Alpha ESS SMILE-B3-PLUS Owner'S Manual Download Page 33

Owner’s Manual

33

Section 5. Fire-fighting measures

Suitable extinguishing media:

In case of fire suitable extinguishing media: carbon dioxide or dry chemical. Use Novec 1230, FM-200, or dioxide extinguisher.

ABC extinguishers are not effective when the battery pack is on fire.

Special hazards arising from chemical:

Contents react with water. May explode if exposed to high temperatures due to pressure build up in battery casing. Lithium may 

burn in a fire situation and may be ejected from the battery. Damaged cells may evolve toxic and flammable vapours.

Specific protective equipment and precautions for firefighters:

Evacuate area and contact emergency services. Toxic gases may be evolved in a fire situation. Remain upwind and notify those 

downwind of hazard. Wear full protective equipment including Self Contained Breathing Apparatus (SCBA) and protective gear in 

compliance with the Directive on Personal Protective Equipment 89/686/EEC when combating fire. Use water fog to cool intact 

containers and nearby storage areas.

Hazchem code:

4 – Dry Agent (water MUST NOT be allowed to come into contact with substance).

W – Risk of violent reaction or explosion. Wear liquid-tight chemical protective clothing and breathing apparatus.  

Contain spill and run-off.

Section 6. Accidental release measures

Personal precautions, protective equipment and emergency procedures:

Wear Personal Protective Equipment (PPE) as detailed in SECTION 8 of this SDS.

Environmental precautions:

See SECTION 12 for additional Ecological Information.

Methods and materials for containment and cleaning up:

If spilt, collect and reuse where possible. If battery is broken or damaged, absorb liquid with sand or similar. Contain spillage, then 

collect and place in suitable containers for disposal. CAUTION: Avoid exposure to contents. For waste disposal, see SECTION 13 

of the SDS.

Section 7. Handling and storage

Precautions for safe handling:

Before use carefully read the product manuals Use of Safe Work Practices are recommended to avoid eye or skin contact and 

inhalation. Observe good personal hygiene, including washing hands before eating. Prohibit eating, drinking and smoking in 

contaminated areas.

Conditions for safe storage, including any incompatibilities:

Store tightly sealed in a cool, dry, well ventilated area, removed from water, incompatible substances, heat or ignition sources 

and foodstuffs. Ensure containers are adequately labelled, protected from physical damage and sealed when not in use. Check 

regularly for leaks or spills. Store within the recommended limit of -20°C to 45°C. Do not expose to high temperature (55°C). Since 

short circuit can cause burn hazard or safety vent to open, do not store with metal jewellery, metal covered tables, or metal belt.

Section 8. Exposure controls / Personal protection

Exposure control measures:

This product presents no health hazards to the user when used 

according to label directions for its intended purposes.

Ingredient

Determinant

Sampling Time

BEI

Polyvinylidene 

Fluoride

Fluoride in urine

Prior to shift

2 mg/L

Fluoride in urine

End of shift

3 mg/L

Biological monitoring:

Control banding:

Control banding is not used.

Engineering controls:

Use local exhaust ventilation or other engineering controls to 

control sources of dust, mist, fume and vapour.

Personal protective equipment (PPE):

Eye Protection: Not necessary under normal use. Wear safety 

goggles if handling a ruptured or leaking battery cell.

Skin Protection: Not necessary under normal use for hands 

and body. Wear PVC or rubber gloves if handling a ruptured or 

leaking battery cell.

Respiratory Protection: Not necessary under normal use. In 

case of battery or cell rupture, use a self-contained full face 

respiratory mask.

Reference: ACGIH Biological Exposure Indices

www.alpha-ess.com

SAFETY DATA SHEETS

Summary of Contents for SMILE-B3-PLUS

Page 1: ...Owner s Manual SMILE B3 PLUS SMILE BAT 5P ...

Page 2: ......

Page 3: ... 1 1 Copyright Declaration This manual is under the copyright of Alpha ESS Co Ltd with all rights reserved Please keep the manual properly and operate in strict accordance with all safety and operating instructions in this manual Please do not operate the product before reading through the manual 1 2 Version Information Version Date Content 1 0 0 May 2022 Owner s Manual CONTACT ...

Page 4: ......

Page 5: ...ciple 4 3 System Operation 4 4 System Operation Status 5 Maintenance 5 1 Function Checks 5 2 System Faults Errors 6 System Monitoring 6 1 Wi Fi Configuration 6 2 System Registration 6 3 Alpha ESS App Features 7 Emergency Situations 7 1 Emergency Handling Plan 7 2 Fire 7 3 Leaking Batteries 7 4 Wet Batteries 7 5 Damaged Decommissioning Battery 8 Warranty Conditions 9 Safety Data Sheets 3 3 3 4 5 8 ...

Page 6: ...ber of batteries S N S N S N S N S N 4 Energy Meters Model Number ACR10R DTSU666 Number of Meters 5 Total Battery Storage Capacity kWh 6 UN Number UN 3480 7 Date of Installation Commissioning 8 Firmware Versions Inverter BMS 9 Initial System Settings Safety Regulation Regional Application Standard AS 4777 2 Australia A Australia B Australia C NZ 10 System Verification Grid Status On Grid Status Of...

Page 7: ...System Operation design principles Further ensure that a copy of the below customer acknowledgement is provided to the system provider for their installation records Customer Acknowledgement I Customer acknowledge that System Provider have attended my property and conducted the requested work I confirm that the installer attending my property has completed the installation based on his her recomme...

Page 8: ...in this document The Electrician should always wear the right Personal Protective Equipment PPE Level 1 while operating the Energy Storage system Do not touch any uninsulated DC cables as this may result in electrical shock or injury Do not open the Inverter and Battery or modify any of the protective devices Do not dispose of batteries in fire as the batteries may explode Only use the Battery sys...

Page 9: ...o not short circuit the battery module or allow them to come in contact with metal Do not continue to use the battery module after a short circuit Do not install the battery pack in the vicinity of any equipment containing flammable gases or liquids If the moisture penetrates the system e g due to casing damage please do not operate the system and contact Alpha ESS immediately for further troubles...

Page 10: ...he inverter observe a waiting time of 5 minutes WEEE designation Do not dispose of the product together with household waste but in accordance with disposal regulations for electronic waste applicable at the installation site Observe the documentation Certified safety The product is TUV tested and complies with the requirements of the EU Equipment and Product Safety Act CE marking The product comp...

Page 11: ...sk of chemical burns to skin Risk of explosion Risk of electrolyte leakage Use eye protection Fire naked flame and smoking prohibited Install out of reach of children Recycling code Marking for transport of dangerous goods The product passes the certifications of the UN38 3 ...

Page 12: ... wide array of system functions In addition the system allows the end user flexibility to add on more capacity based on their energy requirements The simple plug and play installation allows the installer to connect the additional storage units in quick succession reduce overall time spent on site The SMILE B3 PLUS use the safest battery chemistry available on the market Lithium Iron Phosphate LFP...

Page 13: ... Product Warranty 10 Year Battery Warranty Inverter Technical Specifications Max AC Input Current 13 A Max AC Short Circuit Current 18 75 A Nominal AC Input Voltage 230 V Battery Voltage Range 40 58 V Max Charging Discharging Current 60 A Max Charging Discharging Power 3000 VA Rated Output Backup Power 3000 VA Phase Single Phase Max Altitude 3000m Max Efficiency 96 Safety IEC 62619 AS 62040 1 2019...

Page 14: ...e 1 kW 4 3 System Operation The system must be turned On Off in the correct sequence to avoid any damage Switching on Turn on the Main Switch Energy Storage Battery within the switchboard Turn on the Solar PV Inverter Main Switch within the switchboard If AC Isolator is connected on Grid side turn it on Short press the Power button on the right side of the Primary Unit then switch on the battery b...

Page 15: ...ide Turn off the Main Switch Energy Storage Battery within the switchboard 4 4 System Operating Status On the Primary Unit SMILE B3 PLUS there are three LEDs indicating the status of system parameters i e Normal operation System Fault and COM communication The table below describes different LED states and their description Battery Display Com Fault Normal LED Status Description Normal Solid Green...

Page 16: ...ndby mode Green light flickering 1s Work mode Green light flickering 10s Protection Codes LED Ring Protection Code LED Display Description Green light flickering every 3 seconds 1 Temperature difference 3 High temperature 4 Low temperature discharge 5 Over current charge 6 Over current discharge 8 Cell overvoltage 9 Cell under voltage 11 Low temperature charge 5 Maintenance It s recommended that r...

Page 17: ...tem is capable of self remote diagnosis whilst operating in Protection mode and is expected to return to normal operation thereafter Please contact your system provider or Alpha ESS if the protection code persists for an extended period If the system displays an Error Code as shown below please contact your installer or system provider urgently for further resolution Do not attempt to resolve the ...

Page 18: ...ore apple com Android Alpha ESS Apps on Google Play 6 1 Wi Fi configuration Launch the APP click Wi Fi configuration and follow the prompts to connect the WiFi module Link the SMILE B3 PLUS Wi Fi module named after the product S N format AL xxxxx to your home Wi Fi network When prompted enter the password 12345678 select Connect ...

Page 19: ...ully Configured message the Green LED COM on the Primary unit comes on Flashing followed by Solid Select the type of Grid PV Meters used on site either CT Meter based on site conditions Select the applicable Safety Regulation AS 4777 2 and Regional Application standard Aus A Aus B Aus C Also select the applicable Max Feed in limit and press Submit Note The Basic Parameters are usually completed by...

Page 20: ...lete account registration Note If you have forgotten your password click Forgot Password on the login page to reset your password Enter your username and e mail to receive instructions on your mailbox Follow the prompts in the e mail to create a new password 6 3 Alpha ESS App Features Login to the Alpha ESS app using your credentials to access your SMILE B3 PLUS system information Homepage The hom...

Page 21: ...hows the real time power diagram for a demo system All values are displayed in Watts W Description PV Real time Solar generation Grid Real time feed in arrow facing towards grid or grid consumption arrow facing towards loads Battery Real time Battery charge and discharge Load Real time Overall house Load SoC Real time battery capacity Power Diagram Click Power on the home page to view the power ma...

Page 22: ...sponding to that period Users can toggle between Day Month Year and Since Installation to view appropriate profit data as shown below The app also displays the Total Income and Total Investment depending on the Values set by the user installer Description All values are calculated in as set by the customer installer Feed in Income from grid feed in as per applicable feed in tariff Self consumption...

Page 23: ... ToU charge function on the SMILE B3 PLUS that allows for charging during Off peak hours at low electricity prices and discharging towards the house loads during Peak Shoulder hours at high electricity prices This feature can be accessed by selecting Setting from the homepage and then Time Of Use Charging Select Charge Batteries from Grid ON Under Charging Period 1 select START END times correspon...

Page 24: ...tective Equipment are permitted to access the Battery installation area Please ensure that the following equipment is available near the system SCBA self contained breathing apparatus and protective gear in compliance with the Directive on Personal Protective Equipment 89 686 EEC Novec 1230 FM 200 or dioxide extinguisher Note ABC extinguishers are not effective when the battery pack is on fire Bat...

Page 25: ...are dangerous and must be handled with the utmost care They are not fit for use and may pose a danger to people or property If the battery pack seems to be damaged contact Alpha ESS or an authorised system provider to organise an electrician to remove the battery and return the product for further troubleshooting If the battery needs to be decommissioned please refer to the local national codes an...

Page 26: ...properly certified battery installer CEC approved and correctly followed the installation manual General Terms We warrant that we will repair or replace at our option a Product or any part thereof if such Product is faulty or defective in manufacture or materials for a period of 5 years product warranty 10 years battery performance warranty for SMILE BAT 5P SMILE B3 PLUS from the earlier of i the ...

Page 27: ... internet the warranty is then reduced to 3 years Each time a warranty claim is made against a system that has no internet connection the installer or the end user is obliged to organise qualified personnel to conduct an on site inspection and data collection under the instruction of AlphaESS We monitor systems and inform end customers via internet in the event of defects in the material or workma...

Page 28: ...r failures due to incorrect installation or commissioning are not covered under this Warranty Where a Product or part thereof is replaced or repaired under this Warranty the balance of the original Warranty period will apply The replacement product or part s do not carry a new voluntary warranty The Product must have its original serial number and rating labels intact and readable Define following...

Page 29: ...fied or normal operating ranges for such Products as a result of changes which occur in the condition or operational performance of the Product due to climate or other environmental influence foreign material contamination e g dirt smoke salt chemicals and other impurities water entry exposure to excessive heat or solvents or because of use of the Product with insufficient ventilation in particula...

Page 30: ...nd user must stop using the Product or the system in which the Product is installed as the case may be by isolating the Product from any energy source make a claim as soon as possible and follow all instructions provided by us or our representative or agents To make a Warranty claim under this voluntary warranty the end user must contact us by the customer feedback system in online monitoring http...

Page 31: ...to prevent re occurring of the warranty failures It is therefore critical that all claims under this Warranty are promptly submitted to us as soon as the Product fails and in any event within three months of knowledge of the matter of event giving rise to the claim No consideration will be given to claims under this Warranty which are made after this period Product Liability and Product Safety We ...

Page 32: ... Moreover if heated strongly by the surrounding fire acrid or harmful fume may be emitted Chemical Name CAS No Weight 10 1 Weight B3 SPCC Fe 7439 89 6 15 20 20 25 Lithium Iron Phosphate LFP 15365 14 7 26 30 18 20 Iron 7439 89 6 11 14 13 16 Lithium Hexafluorophosphate 21324 40 3 10 12 10 12 Copper Metal 7440 50 8 8 12 8 12 Carbon 7440 44 0 5 8 5 8 Aluminium Metal 7429 90 5 3 7 3 7 Polyester Resin 6...

Page 33: ...contents For waste disposal see SECTION 13 of the SDS Section 7 Handling and storage Precautions for safe handling Before use carefully read the product manuals Use of Safe Work Practices are recommended to avoid eye or skin contact and inhalation Observe good personal hygiene including washing hands before eating Prohibit eating drinking and smoking in contaminated areas Conditions for safe stora...

Page 34: ... Chemical Stability Stable under normal use Possibility of hazardous reactions Polymerisation will not occur Conditions to avoid Heat above 70 C or incinerate Deform Mutilate Crush Pierce Disassemble Recharge Short circuit Expose over a long period to humid conditions Incompatible materials Battery contents are incompatible with water evolving flammable gas oxidising agents e g hypochlorites acids...

Page 35: ... Ion Batteries packed contained in equipment Transport Hazard Class 9 9 9 Packing Group II II II LAND TRANSPORT ADG SEA TRANSPORT IMDG IMO AIR TRANSPORT IATA ICAO UN Number 3480 3480 3480 Proper Shipping Name Lithium Ion Battery Lithium Ion Battery Lithium Ion Battery Transport Hazard Class 9 9 9 Packing Group II II II Persistence and degradability Not determined Bioaccumulative potential Not dete...

Page 36: ...Alpha ESS Australia Pty Ltd Unit 1 2 Ralph Street Alexandria NSW 2015 AUSTRALIA 61 1300 968 933 www alpha ess com au australia alpha ess com ...

Reviews: