Warning
The frame of photovoltaic array should be ground connection to make sure the safety of operating personnel.
When the photovoltaic array is exposed to light, it supplies a DC voltage to the PCS.
Warning
To be in compliance EN61000-3-11, the product shall be connected only to a supply of the system impedance: ∣Zsys∣
=0.191 ohms or less. Before connect the product to public power network, please consult your local power supply
authority to ensure the power network meet above requirement.
Attention
Ensure all wiring is correctly selected and erected in accordance with AS 3000 wiring regulation.
Make sure the neutral conductor of the Grid and load via stand-alone port shall not interrupt.
Make sure the neutral conductor of the Grid and load shall be bonding to earth via earth bar.
Battery
Bank
PCS
Solar
Array
A
B
C
N
PE
U
V
W
Essential
Loads
Grid
Max output
100000VA
N
PE
Neutral bar
MEN
connect
Earth bar
Essential Supply
Grid Supply
Earth
electrode
CT
Over current
protection
Fig.1-3 Connection diagram of the energy storing system
1.4
Operation model
The Bi-directional Hybrid Storage inverter can operate in on-grid model and off-grid model. When the inverter
works in on-grid model, it can trace the amplitude and phase of grid voltage faultlessly. And if the DC source is