26 Chapter VI Operation Control Display Panel
Fig.6-8 AC parameter interface
Enter “AC parameter”. Main setting parameter items
include “inverter control mode”, “active power
setting” and “reactive power setting”, as shown in
Fig. 6-8.
Inverter control mode: please set it as “constant
reactive power”.
Active power setting: Set active power within the
rated power of the machine according to the actual
need.
Reactive power setting: Set reactive power within the
rated power of the machine according to the actual
need.
6.2.4DC parameter interface
Enter “DC parameter. As shown in Fig. 6-9, main parameter settings are introduced as follows.
Fig.6-9 DC parameter interface
DC Work Mode: please set it as “auto”.
EOD V of Batt: Prioritize the setting according to the manufacturer’s recommendation. Conduct setting according
to the following data when manufacturer’s data cannot be obtained: Set 2V lead battery according to 1.67~1.80V*
number of batteries in series; set 3.2V lithium batteries according to 2.70~2.75V* number of batteries in series.
Float CHRG V: Prioritize the setting according to the manufacturer’s recommendation. Conduct setting according
to the following data when manufacturer’s data cannot be obtained: Set 2V lead batteries according to