14
Input Connection
All wiring is conducted on the AC side of the inverter. The SolShare requires a single-phase, grid-connected
inverter to be used in the PV installation. The solar input conductors must come from the inverter(s) while passing
through a system disconnect.
To wire the input conductors in to the SolShare, the following steps should be taken:
1. Measure out the conductors and conduit, and cut to appropriate length.
2. If outdoors, select appropriate conductors/conduit gland and use these to replace membrane glands.
Insert conduit and conductors into SolShare via this conductor/conduit glands.
4. Cut and connect earth ground and neutral from input to their respective connection points. Use two
of the ground screws provided with the SolShare to secure the input ground connection to the Grounding
Electrode Conductors (GEC).
5. Cut and connect phase conductors as per the diagram above.
Neutral Connection
Please refer to Appendix C for Terminal Block Connection options.
1. Run input neutral from inverter and connect to the SolShare’s neutral input connector (as shown above)
2. Run output neutral cable from neutral point in meter panel and connect to the SolShare’s neutral output
connector (as shown above).
Output Power Connection
1. Complete column 2 of the Commissioning Document on page 5, allocating each SolShare output
to a unit/apmt number.
2. Cut output power cables to appropriate length to reach from SolShare output to Unit PV Breakers
(Inverter Supply). Label both ends of these cables with the unit/apmt number.
3. Run cables between SolShare and Unit PV Breakers (Inverter Supply). Terminate cables to appropriate
SolShare output connectors as per the configuration in step 1.
Warning:
Only one neutral output should be wired from SolShare to meter panel.
Important:
The Unit PV Breakers (Inverter Supply) can be mounted on the meter panel or in a separate enclosure
adjacent to meter panel (as pictured on page 8).
Warning:
No wiring loops of excess conductor length are allowed to be made. Field wiring of all circuits must
maintain 1/4” separation from all other circuits.
Warning:
All output cable gauges must be same as input cable gauge.
Warning:
Neutral bonding to protective ground must take place only at the main distribution panel.