4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table 

below.   

 

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 
mains.   

The AC input is connected 
to the UPS output. 

Plug  AC  input  power  cord 
to AC input correctly.   

The icon 

and the warning 

code 

  flash on LCD display 

and alarm is sounding every 2 
seconds. 

EPO function is activated.  Set  the  circuit  in  closed 

position  to  disable  EPO 
function. 

The icons of 

  and 

  and 

the warning code

 

  flash on 

LCD display. Alarm is sounding 
every 2 seconds. 

Line and neutral 
conductors of UPS input 

are reversed. 

Rotate mains power socket 
by  180°  and  then  connect 

to UPS system. 

The icons of 

 

and 

 

and 

the warning code

 

  flash on 

LCD display. Alarm is sounding 
every 2 seconds. 

The external or internal 
battery is incorrectly 
connected. 

Check  if  all  batteries  are 
connected well. 

Fault code is shown as 27 on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too high 

or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 on LCD 
display and alarm is continuously 

sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icons 

  and 

  and the 

warning code

 

 

flash on LCD 

display. Alarm is sounding every 
second. 

UPS is overload.   

Remove excess loads from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 

fed directly by the 
electrical network via the 
Bypass. 

Remove excess loads from 
UPS output. 

After repetitive overloads, 

the UPS is locked in the 
Bypass mode. Connected 
devices are fed directly by 

the mains. 

Remove excess loads from 

UPS output first. Then shut 
down  the  UPS  and  restart 
it. 

Fault code is shown as 49 on LCD 
display and alarm is continuously 
sounding. 

UPS is over input current.  Remove excess loads from 

UPS output. 

Fault code is shown as 43 and the 
icon 

 

is lighting on LCD 

display. Alarm is continuously 

sounding. 

The UPS shut down 
automatically because of 
overload at the UPS 
output. 

Remove excess loads from 
UPS output and restart it. 

Summary of Contents for One V9 1.5K RT

Page 1: ...Version 1 2 One V9 PF1 0 1K 1 5K 2K 3K Online UPS for Rack and Tower Systems User Manual...

Page 2: ...ALLTRONIC GmbH Raiffeisenstra e 11 89438 Holzheim Service Hotline 49 9075 95 88 3 28...

Page 3: ...2 Operating principle 5 2 3 Install the UPS Only for RT Models 5 2 4 Setup the UPS 6 2 5 Battery Replacement Only for RT Models 9 2 6 Battery Kit Assembly Option for RT Models 10 3 Operations 13 3 1...

Page 4: ...by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE ma...

Page 5: ...y occur between the battery terminals and the ground Before touching please verify that no voltage is present Caution Do not dispose of batteries in a fire The batteries may explode Caution Do not ope...

Page 6: ...This is a category C2 UPS product In a residential environment this product may cause radio interference in which case the user many be required to take additional measures only for 220 230 240 VAC sy...

Page 7: ...he original package in a safe place for future use 2 1 Rear panel view One V9 Tower Models 1K 1 5K 2K 3K One V9 RT Models 1K 1 5K 2K 3K 1 Programmable outlets connect to non critical loads 2 Output re...

Page 8: ...ains input EMI RFI filters rectifier PFC inverter battery charger DC to DC converter battery dynamic bypass and UPS output 2 3 Install the UPS Only for RT Models For safety consideration the UPS is sh...

Page 9: ...he UPS indoors in a clean environment where it is away from window and door Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Maintain an ambient temper...

Page 10: ...gative pole of external battery connector in UPS Polarity misconnection will cause UPS internal fault It s recommended to add one breaker between positive pole of battery pack and positive pole of ext...

Page 11: ...lure you may extend the backup time to critical devices by setting shorter backup time for non critical devices Step 4 Communication connection Communication port USB port RS 232 port Intelligent slot...

Page 12: ...d software installation If there no screen shows 1 minute after inserting the CD please execute setup exe file for initiating software installation 2 Follow the on screen instructions to install the s...

Page 13: ...ut the front panel back to the unit 2 6 Battery Kit Assembly Option for RT Models NOTE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure...

Page 14: ...l battery terminals by following below chart Step 3 Step 4 Put assembled battery packs on one side of plastic shells as below chart Cover the other side of plastic shell as below chart Then battery ki...

Page 15: ...her side of plastic shell as below chart Then battery kit is assembly well Battery kit for 6 Batteries 6 BP CH Step 1 Step 2 Remove adhesive tapes Connect all battery terminals by following below char...

Page 16: ...or transfer to Bypass mode if the Bypass enable setting by pressing this button Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input cur...

Page 17: ...mbient temperature output voltage output frequency load current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0...

Page 18: ...4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running a...

Page 19: ...115 120 127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output...

Page 20: ...V LLS Low loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC m...

Page 21: ...equency high loss point from 51Hz to 55HZ Default 53 0Hz For 60Hz output frequency models 61 65Hz setting the frequency high loss point from 61Hz to 65Hz Default 63 0Hz LLS Bypass low Frequency point...

Page 22: ...ternal battery bank is connected 13 Maximum charger current setting Parameter 1 Parameter 2 Interface Setting Set up the charger maximum current For high voltage model with 24 36 48VDC 1 2 4 6 8 10 12...

Page 23: ...ation transformer connection ENA If selected it s allowed to connect to an external output isolation transformer DIS If selected it s not allowed to connect to external output isolation transformer De...

Page 24: ...hen the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving The UPS will also charge the battery at ECO mode Frequency Converter mode When input freque...

Page 25: ...nding every 2 seconds Overload Sounding every second Over input current Sounding 2 beep every 10 seconds Battery is not connected Sounding every 2 seconds Over Charge Sounding every 2 seconds Site wir...

Page 26: ...incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact...

Page 27: ...place the battery Fault code is shown as 2A on LCD display and alarm is continuously sounding The short circuit occurs on the charger output Check if battery wiring of connected external pack is in sh...

Page 28: ...full charged battery 91 full charged battery ECO Mode 96 full charged battery Battery Mode 88 90 BATTERY Battery Type 12V 7AH 12V 9AH 12V 7AH 12V 9AH Numbers 3 3 6 6 Recharge Time 3 hours recover to 9...

Page 29: ...Sinewave EFFICIENCY AC Mode 91 full charged battery ECO Mode 96 full charged battery Battery Mode 88 90 BATTERY Battery Type 12V 7AH 12V 9AH 12V 7AH 12V 9AH Numbers 3 3 6 6 Recharge Time 3 hours recov...

Page 30: ...r or from ALLTRONIC Your Way to ALLTRONIC Headquarter to Germany ALLTRONIC GmbH Raiffeisenstr 11 D 89438 Holzheim Germany Telefon 49 9075 95 88 328 Mail service alltronic net de CostumerCenter https p...

Reviews: