from 120Vac to 140Vac. (Default: 132Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220:
setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115:
setting the low voltage point in parameter 3 from
85Vac to 115Vac. (Default: 85Vac)
⚫
08: Bypass frequency range setting
Parameter 1
Parameter 2
Interface
Setting
Set the acceptable high frequency point and acceptable low
frequency point for Bypass mode by pressing the Down key
or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss point from 51Hz
to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss point from 61Hz
to 65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
⚫
09: Programmable outlets enable/disable
Parameter 1
Parameter 2
Interface
Setting
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
⚫
10: Programmable outlets setting
Parameter 1
Parameter 2
Interface
Setting
Set up backup time limits for programmable outlets.
0-999:
setting the backup time limits in minutes from 0-999
for programmable outlets which connect to non-critical
devices on battery mode. (Default: 999)