Allstyle 4AC13018ASA1 Installation Manual Download Page 4

A  minimum  clearance  of  18”  is  required  for  service  at 

the  control  panel  access.   A  12”  clearance  is  required 

for the air inlet to the outdoor coil around the perimeter 

of the unit.  The air discharge of the unit requires a 60” 

clearance between the top of the unit and any obstruction.  

See Pictorial below.

The length of the refrigerant tubing, between the outdoor 

unit and indoor coil, should be as short as possible to 

avoid capacity and efficiency loss.  Excessive spacing of 

the outdoor unit from the home can lead to the refrigerant 

lines being restricted by trampling or by being punctured 

by lawn mowers.  Locate the outdoor unit away from 

bedroom windows or other rooms where sound might 

not be desirable.

Provide  sufficient  clearance  from  shrubs  to  allow  adequate 

air to pass across the outdoor coil without leaves or branches 

being pulled into the coil.

Consideration should be given to the distance and routing of 

electrical service that would have to be run to connect the 

outdoor unit.

The outdoor unit may be installed at ground level on a solid 

base that will not shift or settle, causing strain on the refrigerant 

lines and possible leaks.  Isolate the base from the structure 

to avoid noise or vibration transmission.  When installing 

units on a roof, a structure should be used to minimize the 

transmission of sound or vibration into the conditioned space.  

Thought should be give to water drainage away from the 

outdoor unit.  Drain holes in the base pan must be kept clear.

SECTION 4.  REFRIGERANT PIPING 

CONNECTIONS

Undersized line sets will increase the refrigerant pressure 

drop between the indoor evaporator and outdoor unit, 

resulting in a decrease in system capacity.  Over sizing 

the line sets may result in excessive refrigerant charge, 

thereby making the system more susceptible to liquid 

migration.  Slope horizontal vapor lines at least 1” every 

20  feet  toward  the  outdoor  unit  to  facilitate  proper  oil 

return.

Use only refrigerant grade (dehydrated and sealed) 

copper tubing of the size indicated in Table 1 to 

interconnect the condensing unit with the indoor 

evaporator.  Take extreme care to keep refrigerant 

tubing clean and dry prior to and during installation.

All outdoor unit and evaporator coil connections are copper to 

copper and should be brazed with a copper alloy material such 

as Silfos-5 or equivalent instead of soft solder.  The outdoor 

units have re-usable service valves on both the liquid and 

vapor connections.  Precautions should be taken to prevent 

heat damage to the valve by wrapping a wet rag around it 

when brazing.  Do not remove plugs from ends of tubing 

until connection is ready to be made.  Suction line insulation 

is necessary to prevent condensation from forming on and 

dropping from suction line.  Apply suction line insulation by 

sliding it on the sealed tubing before cutting and making 

connections.  See Table 1 for correct vapor line size.

Installer’s Information Manual

Page 4

Figure 2. Typical Location and Clearances

Summary of Contents for 4AC13018ASA1

Page 1: ...documents listed above You should become familiar with these instructions as it will be helpful in avoiding any needless service costs or operational problems Keep these instructions as long as you k...

Page 2: ...ou to potential hazards we use the signal words WARNING and CAUTION throughout this manual WARNING alerts you to situations that could cause or result in serious injury or death CAUTION alerts you to...

Page 3: ...n Agency EPA has issued various regulations regarding the introduction and disposal of refrigerants in this unit Failure to follow these regulations may harm the environment and can lead to the imposi...

Page 4: ...d be give to water drainage away from the outdoor unit Drain holes in the base pan must be kept clear SECTION 4 REFRIGERANT PIPING CONNECTIONS Undersizedlinesetswillincreasetherefrigerantpressure drop...

Page 5: ...ighten This opens the valve completely The gauge port is open accessible at all times CAUTION Extreme care should be used when brazing joints Keep torch away from condenser cabinet aluminum coil and p...

Page 6: ...hich have Thermostatic Expansion Valve TXV as the expansion device For proper sub cooling readings a standard high side gauge is required for pressure readings 1 Measure the outdoor air temperature T1...

Page 7: ...ing unit for unusual noise and undue vibration 5 Allow the system to operate until it is balanced or stabilized approximately 30 minutes before making further checks 6 Remove manifold gauge hoses and...

Page 8: ...t Installer s Information Manual Page 8 SUB COOLING CHART FOR UNITS WITH THERMOSTATIC EXPANSION VALVES 18 16 14 12 10 8 6 4 60 65 70 75 80 85 90 95 100 105 110 115 Remove Refrigerant Add Refrigerant S...

Page 9: ...ect voltage Defective overload protector Refrigerant undercharge At compressor terminals voltage must be 10 of nameplate marking when unit is operating Replace check for correct voltage Add refrigeran...

Page 10: ...Installer s Information Manual Page 10...

Page 11: ...Installer s Information Manual Page 11 NOTES...

Page 12: ...Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specification without notice Installer s Information Manual Rev 8 2015...

Reviews: