background image

OPERATION & ADJUSTMENT INSTRUCTIONS 

17 

Setup Modes 

Various operating characteristics can be modified via the setup 
modes. The operator is moved to the close limit position and 
the on-board dip switches (see Figure 15) are 

TEMPORARILY

 

set according to the table at right to enter a Setup Mode. The on 
board OPEN and STOP buttons are used to modify the 
characteristic. Once set, the values are stored in non-volatile 
memory.   
These values are set to factory defaults that should be 
satisfactory for many applications. All values as described here 
can be reset to the factory defaults as follows: 

 

Remove 24 VAC power from the control board. 

 

Press and hold the on-board stop button. 

 

Re-apply 24 VAC while holding the on-board stop button. 

After completing the procedure to modify the operating 

characteristic the switches must be returned to the originally set 
Operating Mode setting (see section previous). 

 

Delay on Reverse Setup 

To help prevent stress on the door components, this feature 

allows for a delay time between the door stopping and reversing 
when a command to reverse is received as the door is closing.  
The factory default time is 0.75 seconds; the minimum time is 
0.4 seconds; the maximum time is 2 seconds.  

After moving the door to the close position and 

temporarily

 

setting the switches to the appropriate settings in the table,  
pressing STOP will reset the time to the minimum setting. 

Every time OPEN is pressed, 200 mS is added to the time (up to 

the maximum). 

Changing the dip-switch setting to any other setting will save 

the new time.  Return the dip switches to the originally set 
Operating Mode setting (see section previous). 

 

Close Limit Delay Setup 

To provide for irregularities in the floor, this feature allows for 

the door to continue to travel down after the Reverse Cutout 
Limit is activated.  The factory default time is 0.32 seconds; the 
minimum time is 0.12 seconds; the maximum time is 0.66 
seconds. 

After moving the door to the close position and 

temporarily

 

setting the switches to the appropriate settings in the table,  
pressing STOP will reset the time to the minimum setting. 

Every time OPEN is pressed, 0.02 seconds are added to the time 

(up to the maximum). 

Changing the dip-switch setting to any other setting will save 

the new time.  Return the dip switches to the originally set 
Operating Mode setting (see section previous). 

 

Mid-Stop Limit Setup 

This features provides a timing function to stop a door as it is 

traveling open at a Mid Stop position instead of the full open 
position.  The door can then be moved to the full open position 
if desired by pressing the Open button. A single button input 
when the door is at the mid stop position will cause the door to 
begin moving in the close direction. The factory default is not 
set; the minimum run time to mid-stop limit is 6 seconds. 

After moving the door to the close position and 

temporarily

 

setting the switches to the appropriate settings in the table,  
pressing STOP will remove the mid-stop limit setting. 

Pressing OPEN will start the door open. When the door reaches 

the desired mid-stop position, press STOP. 

Changing the dip-switch setting to any other setting will save 

the mid-stop limit position.  Return the dip switches to the 
originally set Operating Mode setting (see section previous). 

Note: The door must move a sufficient distance to fully 

disengage the Reverse Cutout Limit nut from the Reverse Cutout 
Limit switch to set the mid-stop limit. 

 

Auto Close Timer Setup  

This feature allows for a modification of the amount of time 

between the door reaching either the Mid Stop or the Full Open 
position and automatically starting in the close direction.  The 
Auto Close feature is only active when the operator is set to the  
T or TS Operating Mode (see section previous).  The factory 
default is 30 seconds; the minimum time is 5 seconds; the 
maximum time is 5 minutes. 

After moving the door to the close position and 

temporarily

 

setting the switches to the appropriate settings in the table,  
pressing STOP will clear and turn off the auto close timer. 

Every time OPEN is pressed, 5 seconds is added to the time. 
Changing the dip-switch settings to any other settings will save 

the new time.  Return the dip switches to the originally set 
Operating Mode setting (see section previous).

 

 

Maximum Run Time Setup  

This feature provides for a maximum amount of time the motor 

will be energized after an input is recognized.  The factory 
default time is 30 seconds; the maximum time is 60 seconds. 

After moving the door to the close position and 

temporarily

 

setting the switches to the appropriate settings in the table,  
pressing STOP will reset the time to the factory default setting. 

Pressing OPEN will start the door open. The run time will be 

recorded when the door reaches the open limit. To prevent 
nuisance problems, 0.75 seconds are added to this time. Pressing 
stop before the door reaches the open limit will stop the door 
and reset the time to the factory default. 

Changing the dip-switch setting to any other setting will save 

the new time

.  

Return the dip switches to the originally set 

Operating Mode setting (see section previous).

 

 

 
  

Setup Mode

 

Switch 1

 

Switch 2

 

Switch 3

 

Switch 4

 

Delay on Reverse 

ON 

ON 

ON 

ON 

Mid-Stop Limit 

ON 

OFF 

ON 

ON 

Auto Close Timer 

OFF 

OFF 

ON 

ON 

Maximum Run Time 

OFF 

ON 

OFF 

ON 

Close Limit Delay  

OFF 

ON 

ON 

ON 

SETUP MODES

 

Summary of Contents for MH5011S

Page 1: ...S JACKSHAFT COMMERCIAL VEHICULAR DOOR OPERATORS READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THIS MANUAL Serial Date Installed Your Dealer 100771 As of date of manufacture meets all ANSI...

Page 2: ...fication Pictorial 4 Important Installation Warnings Things To Do Before During Installation 5 Table 1 Component Identification Listing 5 Installation Instructions 6 12 Figure 2 Operator Footprint 6 F...

Page 3: ...lly Closed reversing devices such as foam or pneumatic reversing door edge components or a three wire photo beam are provided Constant Contact To Close Standard operating mode C2 programmable to Momen...

Page 4: ...carton inspect the nameplate on the cover of the operator control box to verify that it is the correct model for the intended application and that the voltage and phase are in accordance with electri...

Page 5: ...Head 1 2 005031 3 Button Station 1 3 009062 30 Tooth Sprocket 1 Bore 1 4 Key 1 4 009061 20 Tooth Sprocket 1 Bore 1 4 key 1 5 105193 Release Hand Chain Wall Bracket 1 AR As Required ITEM PART DESCRIPT...

Page 6: ...OF THE OPERATOR If the construction permits the operator should be mounted with 3 8 inch diameter bolts through the wall If it is not feasible to go through the wall then use lag bolts to fasten the o...

Page 7: ...of pliers If the chain is too long standard length for 16 foot high doors and below is 26 feet total length of chain shorten it to the desired length using the method described above and discard the...

Page 8: ...100769 100771 FIGURE 5 OPERATOR DIMENSIONS MODEL MJ5011S 8 FIGURE 5A OPERATOR DIMENSIONS MODEL MH5011S...

Page 9: ...everse Cutout Limit nut E and the Reverse Cutout Limit switch A The actual Close Limit position is a timed function whereas the door continues to run for a certain period of time after the Reverse Cut...

Page 10: ...ide the cover of the control box details all of the field wiring terminal connections for the operator Always connect the wires to the push button controls and auxiliary devices exactly as shown Warni...

Page 11: ...ISH PHOTOBEAM 3 WIRE PHOTOBEAM MOTOR CONTROL BOARD Door Edge and Photoelectric Wiring Figure 9 See text on page 10 for operation when Safe Finish or Access Alliance Safe Finish II photo beams are conn...

Page 12: ...is clear PCB 112695 REV B TSLK OPEN C25 PB1 PB2 PB3 U5 STOP CLOSE OPEN C1 R84 R2 R3 D12 COM CLOSE STOP NO REV NC REV PHOTO RADIO 24V R56 R55 R54 PCB 112695 REV B TSLK OPEN RM1 RM2 RM3 VCC COM P7 C25 R...

Page 13: ...cles per hour Permanently install this label adjacent to the door near the push button station at the eye height of the average adult approximately six feet above the above the floor DO NOT over adjus...

Page 14: ...IPPING BECAUSE OF LOOSE OR MISSING HARDWARE BINDING IN THE TRACK RUBBING AGAINST THE DOOR STOPS OR DEFECTIVE OR MISADJUSTED SPRINGS ANY SERVICE REQUIRED TO THE DOOR DOOR SPRINGS OR DOOR OPERATOR MUST...

Page 15: ...f closing door Reverse Momentary activation will reverse a closing door reverse to full open ignores mid stop unless stopped by stop pushbutton input Mid Stop Activation stops an opening door momentar...

Page 16: ...ion to open open override of closing door closes door from mid stop or open limit Reverse Momentary activation will reverse a closing door reverse to full open ignores mid stop unless stopped by stop...

Page 17: ...if desired by pressing the Open button A single button input when the door is at the mid stop position will cause the door to begin moving in the close direction The factory default is not set the min...

Page 18: ...R OBJECT If the operator is equipped with other means of control such as additional 3 button stations or radio controls each of these should be tested separately for proper operation To test the manua...

Page 19: ...O1 D8 U4 C11 R30 R26 R29 C3 C1 C8 R47 R84 R95 SW1 R83 R82 R33 R34 R2 R3 R4 C21 R21 D2 R65 C10 D3 C9 TR4 TR2 R52 C14 TR1 R48 C13 TR3 R89 Q1 C7 D1 D12 R28 R27 C16 LD3 LD2 P2 P3 R1 C30 P1 R31 P6 R57 GROU...

Page 20: ...caused by improper installation or care vandalism or lightning fire or excessive heat flood or other acts of God including but not limited to misuse abuse or alterations failure to provide reasonable...

Reviews: