# NAME
DESCRIPTION
1 24 VAC
Provides maximum 10 VA auxiliary
power for accessories.
2 24 VAC
Provides maximum 10 VA auxiliary
power for accessories.
3 ALTERNATE
Momentary input, must be released
and re-entered to be recognized.
This input is used for “COMMAND OPEN/COMMAND CLOSE”
applications. The 1st signal will cause the gate to begin opening.
A 2nd signal received during the open cycle will stop the gate
immediately. A 3rd signal will close the gate. Connect
appropriate access control devices to this terminal and #16
COMMON. Disable the Close Timer (rotate pot fully counter-
clockwise).
4 RADIO OPEN
Momentary input, must be released
and re-entered to be recognized.
Once activated the gate will open fully. Activation while the gate
is closing will cause it to re-open.
5 FREE EXIT
Momentary or continuous input.
Once activated the gate will open fully. Activation while the gate
is closing will cause it to re-open. Continuous activation while the
gate is open will prevent the Timer-To-Close function from
automatically closing the gate.
6 OPEN
Momentary or continuous signal.
On/Off mode set by Switch #1
WITH SWITCH 1 OFF:
Once activated the gate will open fully.
Activation while the gate is closing will cause it to re-open.
Continuous activation while the gate is open will prevent the
Timer-To-Close function from automatically closing the gate.
Continuous signal required to move the gate when in the alarm
mode.
WITH SWITCH 1 ON:
Gate does not respond to
pushbutton input when in the normal mode. Continuous signal
required to move the gate when in the alarm mode.
7 CLOSE
Momentary or continuous signal.
On/Off mode set by Switch #1
WITH SWITCH 1 OFF:
Once activated the gate will close fully.
Activation while the gate is opening has no effect. Continuous
signal required to move the gate when in the alarm mode.
WITH SWITCH 1 ON:
Gate does not respond to pushbutton input
when in the normal mode. Continuous signal required to move the
gate when in the alarm mode.
8 STOP
Momentary or continuous signal.
10 CLOSE PHOTO
Momentary or continuous signal.
This input is active only when referenced to the closing direction, it
has no effect on the gate when opening or about to open. If
activated when the gate is closing the gate will stop, pause and
reverse in the open direction for 1/2 second (approx. 2 inches)
and stop. Continuous activation will prevent the gate from moving
in the close direction. When the input is removed normal
operation is resumed. If the Timer-To-Close function initiated the
close movement and Switch S2 (Re-close) is ON, the gate will
automatically re-close from a partially closed position after the
input to Close Photo is removed. Continuous activation while the
gate is open will prevent the Timer-To-Close function (if enabled)
from automatically closing the gate.
Overrides all other signals. Once activated, the gate will
immediately stop and await a new command. If the STOP input is
continuously activated, the gate will not move.
# NAME
DESCRIPTION
10 CLOSE PHOTO
(CONT.)
Momentary or continuous signal.
12 OPEN EDGE
Momentary or continuous signal.
This input is active only when referenced to the opening direction, it
has no effect on the gate when closing or about to close. If activated
when the gate is opening the gate will stop, pause and reverse in the
close direction for 1/2 second (approx. 2 inches) and stop. Continuous
activation will prevent the gate from moving in the open direction. If a
second activation occurs before the limit switch is activated the gate
will stop and a require a renewed, intended input to move in the open
direction and before an automatic activation device (timer, etc.) will
operate. This input is intended for Electric Gate Edge systems and
other minimum-contact devices as appropriate. Connect here and to
terminal #16 COMMON. Multiple devices may be connected in
parallel.
13 CLOSE EDGE
Momentary or continuous signal.
This input is active only when referenced to the closing direction, it has
no effect on the gate when opening or about to open. If activated when
the gate is closing the gate will stop, pause and reverse in the open
direction for 1/2 second (approx. 2 inches) and stop. Continuous
activation will prevent the gate from moving in the close direction.
Continuous activation while the gate is open will prevent the Timer-To-
Close function (if enabled) from automatically closing the gate. If a
second activation occurs before the limit switch is activated the gate will
stop and a require a renewed, intended input to move in the close
direction and before an automatic activation device (timer, etc.) will
operate. This input is intended for Electric Gate Edge systems and
other minimum-contact devices as appropriate. Connect here and to
terminal #16 COMMON. Multiple devices may be connected in parallel.
14 MASTER OPEN
Momentary or continuous signal. Master
(output configuration)
This terminal is used to coordinate two independent systems (two
control box/mechanical unit combinations controlling separate gate
leaves). Connects to terminal #6 (OPEN) in the companion control box
and controls the direction of movement in the companion box (Switch
S3 ON).
15 MASTER CLOSE Momentary or continuous signal. Master
(output configuration)
This terminal is used to coordinate two independent systems (two
control box/mechanical unit combinations controlling separate gate
leaves). Connects to terminal #7 (CLOSE) in the companion control
box and controls the direction of movement in the companion box
(Switch S3 ON).
16 COMMON
Common connection for low voltage signal
inputs, terminals 3 through 15.
This input is intended for photoelectric eye systems and other non-
contact devices as appropriate. Connect here and to terminal #16
COMMON. Multiple devices may be connected in parallel.
11
This input is active only when the gate is closing or when it’s fully open
and the Close Timer is operative. All stand-alone vehicle detectors,
photo-eyes and active edges should be connected here and to
terminals #16 COMMON. Multiple devices may be connected in
parallel.
REVERSE
Momentary or continuous signal.
TERMINAL STRIP REFERENCE CHART
D:
STARTING THE OPERATOR - Terminal Strip Chart
21