506887-01
Page 10 of 78
Issue 1213
Setting and Upflow Unit
When the side return air inlets are used in an upflow
application, it may be necessary to install shims on the
bottom of the furnace.
Horizontal Applications
The A97USMV furnace can be installed in horizontal
applications with either right or left hand air discharge.
Refer to Figure 11 for clearances in horizontal applications.
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a
crawlspace. Either suspend the furnace from roof rafters or
floor joists, as shown in Figure 12 or install the furnace on a
platform, as shown in Figure 13. A horizontal suspension kit
(51W10) may be ordered or use equivalent.
NOTE:
Heavy gauge sheet metal straps may be used to
suspend the unit from roof rafters or ceiling joists. When
straps are used to suspend the unit in this way, support must
be provided for both the ends. The straps must not interfere
with the plenum or exhaust piping installation.
Cooling coils
and supply and return air plenums must be supported
separately.
NOTE:
When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1.
Select location for unit keeping in mind service and other
necessary clearances. See Figure 11.
2.
Construct a raised wooden frame and cover frame with
a plywood sheet. If unit is installed above finished space,
fabricate an auxiliary drain pan to be installed under unit.
Set unit in drain pan as shown in Figure 13. Leave 8
inches for service clearance below unit for condensate
trap, unless trap is installed remotely.
3.
Provide a service platform in front of unit. When
installing the unit in a crawl space, a proper support
platform may be created using cement blocks.
4.
Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5.
If necessary, run the condensate line into a condensate
pump to meet drain line slope requirements. The pump
must be rated for use with condensing furnaces. Protect
the condensate discharge line from the pump to the
outside to avoid freezing.
6.
Continue with exhaust, condensate and intake piping
installation according to instructions.
Typical Horizontal Application
Figure 12
Figure 11
Horizontal Application
Installation Clearances
Right-Hand Discharge
* Front
0
Back
0
Ends
0
Vent
Floor
0
0‡
Top
0
* Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** An 8” service clearance must be maintained below the unit to
provide for servicing of the condensate trap. Unless the trap is
mounted remotely.
‡ For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other than
wood flooring.
Summary of Contents for A97USMV
Page 3: ...506887 01 Page 3 of 78 Issue 1213 A97USMV Exploded View Figure 1 ...
Page 16: ...506887 01 Page 16 of 78 Issue 1213 Figure 17 ...
Page 28: ...506887 01 Page 28 of 78 Issue 1213 Trap Drain Assembly using 1 2 PVC or 3 4 PVC Figure 38 ...
Page 35: ...506887 01 Page 35 of 78 Issue 1213 ...
Page 36: ...506887 01 Page 36 of 78 Issue 1213 Figure 46 ...
Page 39: ...506887 01 Page 39 of 78 Issue 1213 ...
Page 40: ...506887 01 Page 40 of 78 Issue 1213 Typical A97USMV Wiring Diagram Figure 47 ...
Page 41: ...506887 01 Page 41 of 78 Issue 1213 Integrated Control Figure 48 ...
Page 42: ...506887 01 Page 42 of 78 Issue 1213 Low Voltage Field Wiring Table 14 2 Stage Single Stage ...
Page 46: ...506887 01 Page 46 of 78 Issue 1213 BLOWER DATA ...
Page 47: ...506887 01 Page 47 of 78 Issue 1213 BLOWER DATA ...
Page 48: ...506887 01 Page 48 of 78 Issue 1213 BLOWER DATA ...
Page 49: ...506887 01 Page 49 of 78 Issue 1213 BLOWER DATA ...
Page 50: ...506887 01 Page 50 of 78 Issue 1213 BLOWER DATA ...
Page 51: ...506887 01 Page 51 of 78 Issue 1213 BLOWER DATA ...
Page 52: ...506887 01 Page 52 of 78 Issue 1213 BLOWER DATA ...
Page 53: ...506887 01 Page 53 of 78 Issue 1213 BLOWER DATA ...
Page 54: ...506887 01 Page 54 of 78 Issue 1213 BLOWER DATA ...
Page 55: ...506887 01 Page 55 of 78 Issue 1213 TABLE 22 ...
Page 56: ...506887 01 Page 56 of 78 Issue 1213 TABLE 23 ...
Page 60: ...506887 01 Page 60 of 78 Issue 1213 Figure 50 ...
Page 68: ...506887 01 Page 68 of 78 Issue 1213 ...
Page 69: ...506887 01 Page 69 of 78 Issue 1213 ...