508151-01
Issue 2104
Page 10 of 72
Display
Action (when button released)
No change (idle)*
Action (when button released)
Solid “E”
Remain in idle mode
Solid “F”
Enter diagnostic recall mode
Solid “P” (variable speed only)
Program unit capacity/size unit (Unit Code)
Two horizontal bars
Soft disable
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal,
active error code, heat state, etc.)
Table 4. Integrated Control Diagnostic Modes
The seven-segment diagnostic LED displays operating
status, target airflow, error codes and other information.
Table 5 lists diagnostic LED codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the
seven-segment diagnostic LED. This button is used to
enable the Error Code Recall “E” mode, the Flame Signal
“F” mode and “P” the Program Unit Capacity/Size mode.
Press the button and hold it to cycle through a menu of
options. Every five seconds a new menu item will be
displayed. When the button is released, the displayed item
will be selected. Once all items in the menu have been
displayed, the menu resumes from the beginning until the
button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10
error codes. Select “c” from the Error Code Recall menu
to clear all error codes. Button must be pressed a second
time while “c” is flashing to confirm command to delete
codes. Press the button until a solid “≡” is displayed to exit
the Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the flame signal mode.
The integrated control will display the flame current on
seven-segment LED in in micro amps (uA).
Flame signal mode is exited after any of the following:
•
Power is reset
•
Pressing and holding push button until 3 horizontal
lines “≡” are displayed
•
10 minutes after entering the flame sense mode.
Program Unit Capacity/Size Mode
After the “P” is selected (by releasing the push button)
the integrated control will start flashing the “P” on display
for 90 seconds. If push button is pressed again and held
during that time, the control will start to display characters
corresponding to different variable speed furnace models
for 3 seconds each. While the wanted character-model is
displayed push button has to be released. Selected option
will flash display for 10 seconds and during that time push
button has to be pressed and held for 5 seconds. Once
control accepts new setting it will store data in non-volatile
memory and reset itself. If 10 seconds expires or push
button is held less than 5 seconds, control will exit field
test mode and go into idle without changing programming
the unit size.
Soft Disable
Soft disabling is when thermostat finds a device on the
BUS that it does not recognize and the thermostat sends
a the device a message to be in soft disabling mode until
properly configured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying
the soft disable code.
1.
Confirm proper wiring between all devices (thermostat,
damper control module, indoor and outdoor).
2.
Cycle power to the control that is displaying the soft
disable code.
3.
Put the room thermostat through set up.
4.
Go to setup / system devices / thermostat / edit / then
push reset.
5.
Go to setup / system devices / thermostat / edit / then
push resetAll.