507762-01
Issue 1907
Page 40 of 46
Unit Start-Up
FOR YOUR SAFETY READ BEFORE OPERATING
Do not use this furnace if any part has been underwater.
A flood-damaged furnace is extremely dangerous.
Attempts to use the furnace can result in fire or explosion.
Immediately call a qualified service technician to inspect
the furnace and to replace all gas controls, control
system parts, and electrical parts that have been wet or
to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or
product or property damage. Should the gas
supply fail to shut off or if overheating
occurs, shut off the gas valve to the furnace
before shutting off the electrical supply.
WARNING
Before attempting to perform any service or
maintenance, turn the electrical power to unit OFF at
disconnect switch.
CAUTION
BEFORE LIGHTING
the unit, smell all around the furnace
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
The gas valve on the 95G1UHEX is equipped with a gas
control switch (lever). Use only your hand to move switch.
Never use tools. If the the switch will not move by hand, do
not try to repair it. Force or attempted repair may result in
a fire or explosion.
Placing the Furnace into Operation
95G1UHEX units are equipped with an automatic hot
surface ignition system. Do not attempt to manually light
burners on this furnace. Each time the thermostat calls for
heat, the burners will automatically light. The ignitor does
not get hot when there is no call for heat on these units.
Priming Condensate Trap
The condensate trap should be primed with water prior
to start-up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1. Follow the lighting instructions to place the unit into
operation.
2. Set the thermostat to initiate a heating demand.
3. Allow the burners to fire for approximately 3 minutes.
4. Adjust the thermostat to deactivate the heating
demand.
RED LED Flash Code
2
Diagnostic Codes / Status of Furnace
Off
No power to control or board fault detected
Heartbeat
1
Normal Operation - Idle, Continuous Fan, Cool
Continuous Rapid Flash
Call For Heat / Burner Operation
1
Reverse Line Voltage Polarity
2
Improper Earth Ground
3
Burner failed to light, or lost flame during heat demand
4
Low Flame Signal - check flame sensor
5
Watchguard - burner failed to light, exceeded maximum number of retries or recycles.
6
Ignitor Circuit Failure - not available on this control
7
Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer than 3 minutes
8
Rollout Switch Open
9
Pressure Switch failed to close or opened during heat demand
10
Watchguard - Pressure Switch opened 5 times during one heat demand
11
Pressure Switch stuck closed prior to activation of combustion air inducer
12
Flame Sensed without gas valve energized
13
Low Line Voltage
NOTE
: A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating
NOTE
: Error codes are indicated by a “rapid flash” - the LED flashes X times at ½ second on ½ second off, remains off for 3 seconds
then repeats.
NOTE
: Last 10 error codes are stored in memory including when power is shut off to the unit. - To recall, press and release button,
most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold
button longer than 5 seconds.