507762-01
Issue 1907
Page 37 of 46
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
Electrostatic discharge can affect
electronic
components.
Take
precautions to neutralize electrostatic
charge by touching your hand and tools
to metal prior to handling the control.
CAUTION
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product
may result in a fire, causing property damage, severe
injury or death. Use copper wire only with this product.
WARNING
MAKE-UP
BOX
Right Side
Remove and relocate
plug to unused
opening on left side
Figure 59. Interior Make-Up Box Installation
The unit is equipped with a field make-up box. The makeup
box may be moved to the right side of the furnace to
facilitate installation. Secure the excess wire to the existing
harness to protect it from damage.
Refer to Figure 61 for field wiring, schematic wiring diagram
and troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE:
Unit nameplate states maximum current draw.
Maximum Over-Current Protection allowed is 15 AMP.
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specifications bulletin (EHB)
and unit rating plate.
CAUTION
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat check to make sure the
wires will be long enough for servicing at a later date. Make
sure that thermostat wire is long enough to facilitate future
removal of blower for service.
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring diagram
shown in Figure 61. Use 18-gauge wire or larger that is
suitable for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70) for the USA
and current Canadian Electric Code part 1 (CSA standard
C22.1) for Canada. A green ground wire is provided in the
field make-up box.
NOTE:
The 95G1UHEX furnace contains electronic
components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace integrated control. See Figure 60 for integrated
control configuration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral
leg of the circuit being connected to one of the provided
neutral terminals. If an accessory rated at greater than one
amp is connected to this terminal, it is necessary to use an
external relay.
One line voltage “120 HUM” 1/4” spade terminal is provided
on the furnace integrated control. See Figure 60 for
integrated control configuration. This terminal is energized
in the heating mode when the combustion air inducer is
operating. Any humidifier rated up to one amp can be