BLOWER PERFORMANCE DATA
Downflow
Model
Motor
Size
(hp)
Blower
Size
Temp.
Rise
(°F)
Blower
speed
Heating cfm @ .10” - .80” w.c.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
A93DF1E045B12A
1/2
10 x 8
25 - 55
High
1395
1365
1330
1305
1275
1245
NA
NA
Med/High
1270
1245
1215
1180
1140
1110
1080
1030
Med
1145
1105
1070
1025
980
950
910
870
Med/Low
845
795
740
700
660
615
585
545
Low
695
640
575
530
485
445
390
335
A93DF1E070B12A
1/2
10 x 8
40 - 70
High
1380
1345
1325
1295
1260
1235
1185
NA
Med/High
1265
1240
1215
1175
1135
1105
1080
1040
Med
1140
1090
1060
1025
985
955
910
865
Med/Low
860
810
770
710
670
620
585
540
Low
700
645
590
530
490
440
395
340
A93DF1E090C16A
3/4
10 x 10
45 - 75
High
1695
1680
1640
1605
1575
1550
1490
NA
Med/High
1495
1445
1410
1385
1355
1310
1265
1240
Med
1365
1315
1285
1245
1215
1165
1125
1075
Med/Low
1265
1240
1200
1160
1115
1085
1030
995
Low
1160
1110
1070
1020
975
925
885
825