507271-02
Page 41 of 52
Issue 1621
Unit Size
0 - 4500 ft
(0 - 1373m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045
No Change
No Change
11J09
070
No Change
11J12
10U93
090
No Change
11J11
10U93
110
No Change
11J12
10U93
135
No Change
11J11
10U93
A95 and 95G1 Pressure Switch Requirements at Varying Altitudes
Pressure switch is factory set. No adjustment necessary. All models use the
factory-installed pressure switch from 0-4500 feet (0-1371 m).
Unit Size
0 - 4500 ft
(0 - 1371m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
All
No Change
No Change
93W88
A93 and 92G1 Pressure Switch at Varying Altitudes
Pressure switch is factory set. No adjustment necessary. All models use the
factory-installed pressure switch from 0-7500 feet (0-2286 m).
Unit
Size
0 - 7500 ft
(0 - 2286 m)
7501 - 10000 ft
(2286 - 3048 m)
Natural
to
LP/Propane
LP/Propane
to
Natural
High Altitude
Natural
Burner Orifice
Kit
High Altitude
LP/Propane
Burner Orifice
Kit
All
11K50+
73W80*
51W01
11K45+
Burner Orifice Conversion Kits at Varying Altitudes
* Conversion requires installation of a gas valve regulator spring which is provided with the
gas conversion Kit.
+ LP Kits include low line pressure switch.
Summary of Contents for 92G1DF-P
Page 17: ...507271 02 Page 17 of 52 Issue 1621 A95DF 95G1DF and A93DF 92G1DF Table 7 ...
Page 18: ...507271 02 Page 18 of 52 Issue 1621 A95DF 95G1DF and A93DF 92G1DF Table 8 ...
Page 31: ...507271 02 Page 31 of 52 Issue 1621 Figure 49 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 36: ...507271 02 Page 36 of 52 Issue 1621 Figure 56 Typical Wiring Diagram For A93DF 92G1DF ...
Page 37: ...507271 02 Page 37 of 52 Issue 1621 Typical Wiring Diagram Figure 57 For A95DF 95G1DF ...
Page 50: ...507271 02 Page 50 of 52 Issue 1621 Start Up Performance Check List ...