508219-01
Issue 2132
Page 10 of 43
Technical Specifications - 4SCU14LB-7
MODEL NUMBER GUIDE
Minor Revision Code
Major Revision Code
Electrical
P - 208 - 230v/60hz/1Ph
Tonnage
18, 24, 30, 36, 42, 48, 60
Region Restriction
1 = all Regions
R = Region-restricted model; not for
installation in the Southwest region
Refrigerant
4 = R410A
SCU
Split Air Conditioner
SEER
14
Tier
LB = Louvered Basic
4 SCU 14 LB 1 24 P - 7 A
PHYSICAL AND ELECTRICAL DATA
Model
Voltage/Hz/
Phase
Voltage
Range
Min.
Circuit
Amp.
Max. Over
Current
Device
(amps)
Compressor
Fan Motor
Refrig.
(oz.)
Shipping
Weight
(lbs.)
Rated
Load
(amps)
Locked
Rotor
(amps)
Rated
Load
(amps)
Rated
HP
Nom.
RPM
4SCU14LB*18P-7
208-230/60/1
197-253
12.4
20
9.4
56.6
0.7
1/10
1075
77
150
4SCU14LB*24P-7
208-230/60/1
197-253
15.0
25
11.2
60.8
1.0
1/6
825
86
160
4SCU14LB*30P-7
208-230/60/1
197-253
17.0
25
12.8
67.8
1.0
1/6
825
100
180
4SCU14LB*36P-7
208-230/60/1
197-253
18.6
30
14.1
83.0
1.0
1/6
825
102
185
4SCU14LB*42P-7
208-230/60/1
197-253
24.1
40
17.9
113.0
1.7
1/4
825
160
208
4SCU14LB148P-4
208-230/60/1
197-253
22.6
45
19.8
109.0
1.7
1/4
825
174
220
4SCU14LB160P-4
208-230/60/1
197-253
34.8
60
26.4
134.0
1.8
1/3
825
192
253
Note:
Weights listed are unit weights with packaging
+ Factory charged for 15 feet offline set. Adjust per installation instructions.
Summary of Contents for 4SCU14LB
Page 34: ...508219 01 Issue 2132 Page 34 of 43 Wiring Diagram Figure 13 A C Single Phase Wiring Diagram ...
Page 35: ...508219 01 Issue 2132 Page 35 of 43 Figure 14 A C Single Phase Wiring Diagram 59 model only ...
Page 36: ...508219 01 Issue 2132 Page 36 of 43 Figure 15 3 Phase 208 230 Volt ...
Page 37: ...508219 01 Issue 2132 Page 37 of 43 Figure 16 3 Phase 460 Volt ...
Page 41: ...508219 01 Issue 2132 Page 41 of 43 Charge Labels Figure 17 4SCU16LE 4SCU14LB 50 ...
Page 42: ...508219 01 Issue 2132 Page 42 of 43 Figure 18 4SCU14LE LB 4 thru 7 ...