SOUND RATINGS
Model
Sound Power
1
Estimated Sound Pressure (dBA)
2
Approximate Distance
3
3.3 Feet
(1 Meter)
6.6 Feet
(2 Meters)
9.8 Feet
(3 Meters)
4SCU13LE118P-5
72
64
58
54
4SCU13LE124P-5/6
72
64
58
54
4SCU13LE130P-5/6
74
66
60
56
4SCU13LE136P-5/6
74
66
60
56
4SCU13LE142P-5/6
76
68
62
58
4SCU13LE148P-5
77
69
63
59
4SCU13LE160P-5
78
70
64
60
1 Rated in accordance with AHRI standard 270 (2015). AHRI Standard 270 establishes a method of rating outdoor unitary equipment in terms of
Sound Power.
2 Rated in accordance with AHRI standard 275 (2010). AHRI Standard 275 provides the calculations for estimating the A-Weighted Sound Pressure
at a given distance from the equipment. That is a more useful number because that is what humans will hear.
3 Based only on distance factor; other factors may change this value such as:
- Unit location (reflective surfaces adjacent to the unit)
- Barrier shielding sources
- Sound path/elevation
- Outside noise sources
ACCESSORIES
System Accessory
Where Used
Kit Number
Purpose
Liquid Line solenoid
All models
60M52
Prevents liquid migration to the compressor especially for high liquid riser
applications
Low ambient (cooling operation)
All models
34M72
Enables cooling demand down to 30 °F. Will require freeze stat, CC heater
and TXV
Compressor Short Cycle Protector
All models
47J27
Delays compressor start 5-7 minutes to prevent short cycling
Hard Start
18
10J42
Scroll compressors usually do not require hard start; maybe needed for utility
brown-out or low voltage areas
Hard Start
24 thru 60
88M91
Crankcase Heater
18, 24, 30, 36
93M04
Prevents liquid migration to compressor in cold weather
Crankcase Heater
42, 48, 60
93M05
Sound Cover
Factory Installed
Lowers compressor sound level
Loss of Charge Kit
Factory Installed
Protects the compressor if refrigerant charge is too low
Additional System Accessories (indoor section)
TXV Kit
18, 24, 30
H4TXV01
TXVs provide superior refrigerant flow control, comfort and efficiency
compared to pistons
36, 42, 48
H4TXV02
60
H4TXV03
Outdoor Thermostat - electric heat
All models
10Z23
Prevents electric heat operation above specific ambient conditions
Outdoor Thermostat - Mounting box
All models
31461
Mounting box for outdoor thermostat
Freezestat
All models
93G35
Protects the compressor at low suction pressure conditions
Overflow switch
All models
11U75
Turn the system off, if condensate water overflows due to clogged drain pipes
Blower time delay
All models
58M81
Improves system efficiency and comfort
Single point power supply
All models
21H39
Provide single power source in one junction box
Auxiliary blower relay
All models
85W66
Maybe required to select multiple indoor blower speeds
Summary of Contents for 4SCU13LE/B
Page 32: ...508216 01 Issue 2130 Page 32 of 42 Figure 12 A C Single Phase Wiring Diagram Wiring Diagram ...
Page 33: ...508216 01 Issue 2130 Page 33 of 42 Figure 13 A C Single Phase Wiring Diagram 59 model only ...
Page 34: ...508216 01 Issue 2130 Page 34 of 42 Figure 14 3 Phase 208 230 Volt ...
Page 35: ...508216 01 Issue 2130 Page 35 of 42 Figure 15 3 Phase 460 Volt ...
Page 39: ...508216 01 Issue 2130 Page 39 of 42 Charge Labels Figure 16 4SCU13L 3 through 5 ...
Page 40: ...508216 01 Issue 2130 Page 40 of 42 Figure 17 4SCU13L 2 ...
Page 41: ...508216 01 Issue 2130 Page 41 of 42 Figure 18 4SCU13L 1 ...