Allied 4AC13 Installation And Start-Up Instructions Manual Download Page 4

Page 4 of 9

507043-03

Issue  1337

Installation Of Line Sets

  DO NOT fasten liquid or suction lines in direct contact 

with the floor or ceiling joist. Use an insulated or suspen

-

sion type of hanger. Keep both lines separate, and always 

insulate the suction line. Long liquid line runs (30 feet or 

more) in an attic will require insulation. Route refrigeration 

line sets to minimize length.

  DO NOT let refrigerant lines come in direct contact 

with foundation. When running refrigerant lines through 

the foundation or wall, openings should allow for a sound 

and vibration absorbing material to be placed or installed 

between tubing and foundation. Any gap between founda-

tion or wall and refrigeration lines should be filled with a 

vibration damping material.

If ANY refrigerant tubing is buried, provide a 6 inch 

verticle rise at service valve. Refrigerant tubing lengths

up to 36 inches may be buried without further special 

consideration. For lengths above 36 inches, consult 

your local distributor.

  CAUTION

  Before making braze connections, be sure all joints 

are clean. Before heat is applied for brazing, dry nitrogen 

should be flowing through the tubing to prevent oxidation 

and scale formation on the inside of the tubing.

  The following is the recommended method for making 

braze connections at the refrigerant line connections:

  1.  Debur and clean refrigerant tube end with emery 

cloth or steel brush.

  2. Insert tubing into swage fitting connection.

  3. Wrap wet rags over valves to protect from heat.

  4. Allow dry nitrogen to flow through refrigerant lines.

  5.  Braze joint, using a suitable brazing alloy for copper 

to copper joints.

  6.  Quench the joint and tubing with water using a wet 

rag. Leave rag on fitting body and re-wet with water 

to help cool area.

Leak Check

  Refrigeration lines and indoor coil must be checked for 

leaks after brazing and before evacuation. The  

recommended procedure is to apply a trace amount of 

vapor refrigerant (approximately two ounces or 3 psig) 

into the line set and indoor coil, then pressurize with 150 

psig of dry nitrogen. Use a refrigerant leak detector to 

check all joints. The system may also be checked for 

leaks using a halide torch or pressure and soapy solution. 

After completion of leak check, relieve all pressure from 

system before evacuation.

Evacuating And Charging Instructions

  WARNING

It is unlawful to release refrigerants into the atmosphere.

  These outdoor units are pre-charged at the factory 

with adequate refrigerant to handle 

15 feet 

of refrigerant 

tubing.

  1.  Connect the vacuum pump to the center hose of 

the manifold gauge set, the low-pressure manifold 

gauge to the vapor service valve and the  

high pressure manifold gauge to the liquid service 

valve.

  2.  The valves should be kept in the “front seated” 

(closed) position. This will allow evacuation of the 

refrigeration lines and the indoor coil, without dis-

turbing the factory charge in the outdoor unit.

  3.  Follow the vacuum pump manufacturer’s  

instructions. Allow the pump to operate until the 

system has been evacuated down to 300 microns. 

Allow the pump to continue running for an addition-

al 15 minutes. Turn OFF the pump and leave the 

connections secured to the two (2) service valves. 

After 5 minutes, if the system fails to hold 1000  

microns or less, check all connections for tight fit 

and repeat the evacuation procedure.

  4.  Isolate the vacuum pump from the system by  

closing the shutoff valves on the gauge-set.  

Disconnect the vacuum pump.

  5.  After evacuation of the connecting lines, remove the 

service valve cap and fully insert the hex wrench 

into the stem. A back-up wrench is required on the 

valve body to open the valve stem. Back-out  

counterclockwise until the valve stem just touches 

the coined edge.

  Replace service valve cap and torque to  

8-11 ft-lb on 3/8” valves; 12-15 ft-lb on 3/4” valves;  

15-20 ft-lb on 7/8” valves.

Summary of Contents for 4AC13

Page 1: ...SI C1 1993 or current edition and Canadian Electrical Code Part 1 CSA WARNING These instructions are intended as a general guide and do not supersede national state or local codes in any way These instructions must be left with the property owner NOTE Safety Precautions 2 Unit Location Installation 2 Rooftop Installation Recommendations 3 Indoor Coil Piston Selection 3 Refrigeration Line Sets 3 In...

Page 2: ... In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refigerant tubes as directly as possible by avoiding unecessary turns and bends 4 Leave some slack b...

Page 3: ... On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit With clearance less than 2 ft from a second uni With clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section It is mandatory that the...

Page 4: ... for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of...

Page 5: ... wire to ground connection in control box for safety Connect power wiring to contactor High voltage power connections to 3 phase models is made to Pig Tail leads with field supplied splice connectors Contol Wiring The control voltage is 24 VAC NEC Class I insulated 18 AWG is required for control wiring For lengths longer than 150 feet contact your local distributor for technical service Ensure the...

Page 6: ...its with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liqui...

Page 7: ...507043 03 Page 7 of 9 Issue 1337 534773W A C SINGLE PHASE WIRING DIAGRAM Single speed condenser fan ...

Page 8: ...Page 8 of 9 507043 03 Issue 1337 A C SINGLE PHASE WIRING DIAGRAM Multi speed condenser fan 537511 01 ...

Page 9: ...rees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and cause damage to the condenser Periodically debris should be brushed from the condenser coils SHARP OBJECT HAZARD WARNING Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY Use a...

Reviews: