Allied 2HP13 Installation/Start-Up Instructions/Homeowners Information Manual Download Page 3

506162-02

Issue  0847

      Page  3  of   14

Elevate Unit

Elevate unit per local clim ate and code requirem ents to

provide clearance above estim ated snowfall level and
ensure adequate drainage of unit.  Use snow stand in
areas where prolonged freezing tem peratures are
encountered.

If conditions or local codes require the unit be attached

to pad or m ounting fram e, tie down bolts should be used
and fastened through knockouts provided in unit base  pan.

Roof Top Installations

Mount on level platform  or fram e 6 inches above roof

surface.  Place unit above a load-bearing wall and isolate
unit and tubing set from  structure.  Arrange supporting
m em bers to adequately support unit and m inim ize
transm ission of vibration to building.  Ensure roof structure
and anchoring m ethod is adequate for location.  Consult
local codes governing rooftop applications.

Roof m ounted units exposed to winds above 5 m ph

m ay require wind baffles to achieve adequate defrost.  A
sheet m etal baffle should be spaced 6-1/2" from  the fall of
the coil.  The height should cover the face of the coil and
the length should be 6" from  the access panel.

NOTE:

Unit m ust be level to within ± 2

/

 (± 3/8 in./ft) per

com pressor m anufacturer specifications.

Clearance Requirem ents

W hen installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping, and service.  For
proper airflow, quiet operation and m axim um  efficiency.
Position so water, snow, or ice from  roof or eaves cannot
fall directly on unit.

DO LOCATE THE UNIT:

!

W ith proper clearances on sides and top of unit

!

On a solid, level foundation or pad

!

To m inim ize refrigerant line lengths

DO NOT LOCATE THE UNIT:

!

On brick, concrete blocks or unstable surfaces

!

Near clothes dryer exhaust vents

!

Near sleeping area or near windows

!

Under eaves where water, snow or ice can fall
directly on the unit

!

with clearance less than 2 ft. from  a second unit

!

with clearance less than 4 ft. on top of unit

Operating Am bient

T he m inim um  outdoor operating am bient in cooling

m ode is 55

/

F, and the m axim um  outdoor operating

am bient in cooling m ode is 125

/

F.  The m axim um  outdoor

operating am bient in heating m ode is 66

/

F.

Indoor Coil Piston Selection

The outdoor heat pum p section m ust be m atched to a

factory approved indoor section.  It is m andatory that the
installer ensure that the correct piston is installed in the
indoor section.  If necessary rem ove the existing piston and
replace it with the correct piston  See  indoor unit
instructions for details of changing the piston.   Contact
your distributor for accessory piston kits.

Indoor (Cooling) Piston Size

The evaporator coil may use an expansion valve (TXV) in place of piston.

NOTE:

  If a TXV is installed a hard start kit is required on

all m odels with reciprocating com pressors.  See spec
sheet for proper kit selection.

14 SEER Heat Pum p M odels

All 14 SEER heat pum p m odels are only rated with TXV on
the indoor side.

Refrigeration Line Sets

 Use only refrigerant grade copper tubes.  Split

system s m ay be installed with up to 50 feet of line set (no
m ore than 20 feet vertical) without special consideration
(see long line set guidelines). 

Accum ulation of water and ice in base pan m ay
cause equipm ent dam age.

13 SEER Heat Pum p Indoor Piston Sizes

Unit Size

2HP13

4HP13

18

.055

.051

24

.063

.055

30

.068

.059

36

.076

.070

42

.076

.070

48

.082

.082

60

.098

.082

14 SEER Heat Pum p Indoor TXV

Unit Size

TXV Kit

18 thru 36

TXV3

42 thru 48

TXV5

Summary of Contents for 2HP13

Page 1: ...l Code Part 1 CSA C22 1 2HP13 14 4HP13 SPLIT SYSTEM HEAT PUMP INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residential and light commercial type buildings Heat Pumps may only be installed with indoor combinations listed in the Air Conditioning and Refrigeration Institute ARI Directory of Certified Products Inspect the unit f...

Page 2: ...nnected to factory approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdo...

Page 3: ...rant line lengths DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and t...

Page 4: ...th water using a wet rag Leave rag on fitting body and re wet with water to help cool area Leak Check Refrigeration lines and indoor coil must be checked for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refri...

Page 5: ... at the line side of the contactor in the control box of the outdoor unit Follow the appropriate wiring diagram attached to inside of the access panel Proper circuit protection recommendations are indicated on Unit Rating Plate Time delay fuses are required to prevent blowing due to starting current the current in rush when equipment starts is referred to as the Locked Rotor Amps or LRA A fuse of ...

Page 6: ...or line sets shorter than 15 feet in length remove charge For line sets longer than 15 feet add charge Oil charge is sufficient for all line lengths Before final adjustment is made to the refrigerant charge it is imperative that proper indoor airflow be established Airflow will be higher across a dry coil versus a wet coil Blower charts are calculated with a dry or wet coil basis Recommended airfl...

Page 7: ...ously Filter Drier The outdoor unit is equipped with a bi flow filter drier If replacement is necessary order new dryer according to the service parts manual Emergency Heat Function Room Thermostat An emergency heat function is designed into some room thermostats This feature is applicable when isolation of outdoor unit is required or when auxiliary electric heat is staged by outdoor thermostats W...

Page 8: ... seconds going in and out of the defrost mode when the compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The timed off delay is 5 minutes long The delay help to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is bypassed by placing the timer select jum...

Page 9: ...506162 02 Issue 0847 Page 9 of 14 H P SINGLE PHASE WIRING DIAGRAM ...

Page 10: ...506162 02 Issue 0847 Page 10 of 14 H P 3 PHASE WIRING DIAGRAM ...

Page 11: ... manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat installed Temperature Setting Levers Most heat pump thermostats have 2 temperature selector levers one for heating and one for cooling Set the levers or dials to the desired temperature set points for both heating and cooling Avoid frequent temperature adj...

Page 12: ...s dryers and fall off from trees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surface...

Page 13: ...lete model and serial number b proof of required periodic maintenance installation date and location c an accurate description of the problem W ARRANTY LIMITATIONS 1 This warranty is void if the covered equipment is removed from the original installation site 2 This warranty does not cover damage or defect resulting from a flood wind fire lightning mold or installation and operation in a corrosive...

Page 14: ...506162 02 Issue 0847 Page 14 of 14 NOTES ...

Reviews: