Allied 2HP13 Installation/Start-Up Instructions/Homeowners Information Manual Download Page 11

506162-02

Issue  0847

      Page  11  of   14

Homeowner's Information

Heat Pump Operation

Your new heat pum p has several characteristics that you

should be aware of:

!

Heat pum ps satisfy heating dem and by delivering
large am ounts of 

warm

 air into the living space.  This

is quite different from  gas-or oil-fired furnaces or an
electric furnace which deliver lower volum es of
considerably 

hotter

 air to heat the space.

!

Do Not be alarm ed if you notice frost on the outdoor
coil in the winter m onths.  Frost develops on the
outdoor coil during the heating cycle when
tem peratures are below 45

/

F.  An electronic control

activates a defrost cycle lasting 5 to 15 m inutes at
preset intervals to clear the outdoor coil of the frost.

!

During the defrost cycle, you m ay notice steam  rising
from  the outdoor unit.  This is a norm al occurrence.
The therm ostat m ay engage auxiliary heat during the
defrost cycle to satisfy a heating dem and; however.,
the unit will run to norm al operation at the conclusion
of the defrost cycle.

In case of extended pow er outage...

If the outdoor tem perature is below 50

/

F and power to

your outdoor unit has been interrupted for 6 hours or
longer, observe the following when restoring power to your
heat pum p system .

!

Set the room  therm ostat selector to the "Em ergency
Heat" setting to obtain tem porary heat for a m inim um
of 6 hours.  This will allow system  refrigerant
pressures and tem peratures enough tim e to return
to a stabilized condition.

!

In Em ergency Heat m ode, all heating dem and is
satisfied by auxiliary heat; heat pum p operation is
locked out.  After a 6 hour "warm -up" period, the
therm ostat can then be switched to the "Heat" setting
and norm al heat pum p operation m y resum e.

!

Heat pum ps (in the cooling m ode) rem ove hum idity
from  your hom e.  Depending on the am ount of
m oisture in the air inside your hom e, water will trickle
from  the condensate drain of the cooling coil.

Therm ostat Operation

The wall-m ounted therm ostat controls your air

conditioner.  The therm ostat is available in various
configurations from  different m anufacturers. The

inform ation below is typical for m ost therm ostats.  Ask your
dealer for specific inform ation regarding the m odel of
therm ostat installed.

Tem perature Setting Levers

Most heat pum p therm ostats have 2 tem perature

selector levers:  one for heating and one for cooling.  Set
the levers or dials to the desired tem perature set points for
both heating and cooling.  Avoid frequent tem perature
adjustm ent; turning the unit off and back on before
pressures equalize puts stress on the unit com pressor.

On heat pum p system s, increasing your therm ostat

setting by m ore than 2 degrees m ay cause supplem ental
heaters to turn on, reducing potential energy savings.

Fan Sw itch

In AUTO or INT (interm ittent ) m ode, the blower operates

only when the therm ostat calls for heating or cooling.  This
m ode is generally preferred when hum idity control is a
priority.  The ON or CONT m ode provides continuous
indoor blower operation, regardless of whether the
com pressor or auxiliary heat are operating.  This m ode is
required when constant air circulation or filtering is desired.

System  Sw itch

Set the system  switch for heating, cooling or auto

operation.  The auto m ode allows the heat pum p to
autom atically switch from  heating m ode to cooling m ode to
m aintain predeterm ined com fort settings.  Many heat pum p
therm ostats are also equipped with an em ergency heat
m ode which locks out heat pum p operation and provides
tem porary heat supplied by the auxiliary heat.

Indicating Light

Most heat pum p therm ostats have an am ber light which

indicates when the heat pum p is operating in the
em ergency heat m ode.

Temperature Indicator

The tem perature indicator displays the actual room

tem perature.

Fan Control

For fan control your therm ostat m ay have a Fan

Selection Switch that allows you to run the fan continuously
or cycle it autom atically with the heating or cooling system .
Switch the lever to ON for continuous operation and to
AUTO for autom atic cycling.

For m axim um  com fort satisfaction and continual air

cleaning/filtering, constant fan operation is recom m ended.

ELECTRICAL SHOCK HAZARD!

Turn OFF electric power to unit before perform ing
any m aintenance or rem oving panels or doors.

FAILURE TO DO SO CO ULD RESULT IN BODILY
INJURY OR DEATH.

Summary of Contents for 2HP13

Page 1: ...l Code Part 1 CSA C22 1 2HP13 14 4HP13 SPLIT SYSTEM HEAT PUMP INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residential and light commercial type buildings Heat Pumps may only be installed with indoor combinations listed in the Air Conditioning and Refrigeration Institute ARI Directory of Certified Products Inspect the unit f...

Page 2: ...nnected to factory approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdo...

Page 3: ...rant line lengths DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and t...

Page 4: ...th water using a wet rag Leave rag on fitting body and re wet with water to help cool area Leak Check Refrigeration lines and indoor coil must be checked for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refri...

Page 5: ... at the line side of the contactor in the control box of the outdoor unit Follow the appropriate wiring diagram attached to inside of the access panel Proper circuit protection recommendations are indicated on Unit Rating Plate Time delay fuses are required to prevent blowing due to starting current the current in rush when equipment starts is referred to as the Locked Rotor Amps or LRA A fuse of ...

Page 6: ...or line sets shorter than 15 feet in length remove charge For line sets longer than 15 feet add charge Oil charge is sufficient for all line lengths Before final adjustment is made to the refrigerant charge it is imperative that proper indoor airflow be established Airflow will be higher across a dry coil versus a wet coil Blower charts are calculated with a dry or wet coil basis Recommended airfl...

Page 7: ...ously Filter Drier The outdoor unit is equipped with a bi flow filter drier If replacement is necessary order new dryer according to the service parts manual Emergency Heat Function Room Thermostat An emergency heat function is designed into some room thermostats This feature is applicable when isolation of outdoor unit is required or when auxiliary electric heat is staged by outdoor thermostats W...

Page 8: ... seconds going in and out of the defrost mode when the compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The timed off delay is 5 minutes long The delay help to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is bypassed by placing the timer select jum...

Page 9: ...506162 02 Issue 0847 Page 9 of 14 H P SINGLE PHASE WIRING DIAGRAM ...

Page 10: ...506162 02 Issue 0847 Page 10 of 14 H P 3 PHASE WIRING DIAGRAM ...

Page 11: ... manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat installed Temperature Setting Levers Most heat pump thermostats have 2 temperature selector levers one for heating and one for cooling Set the levers or dials to the desired temperature set points for both heating and cooling Avoid frequent temperature adj...

Page 12: ...s dryers and fall off from trees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surface...

Page 13: ...lete model and serial number b proof of required periodic maintenance installation date and location c an accurate description of the problem W ARRANTY LIMITATIONS 1 This warranty is void if the covered equipment is removed from the original installation site 2 This warranty does not cover damage or defect resulting from a flood wind fire lightning mold or installation and operation in a corrosive...

Page 14: ...506162 02 Issue 0847 Page 14 of 14 NOTES ...

Reviews: