Allied 11K50 Installation Instructions Download Page 2

507369-03

Issue 1737

Page 2 of 4

2.  Remove the heating compartment access panel. Turn 

the  automatic  gas  valve  switch  to  the  OFF  position. 

See Figure 2 and Figure 3.

3. 

Disconnect  the  gas  supply  and  the  two  wires  at  the 

gas valve.

4. 

Remove the burner box cover (if equipped). Remove 

the four manifold securing screws. Slide the manifold/

gas valve assembly out of the burner box.

5. 

Replace  the  burner  orifices  with  the  provided  gas 

orifices.  Torque  to  approximately  35  in-lbs.  Do  not 

use sealant on orifices. Figure 4 and Figure 5 show 

manifold/gas valve assembly.

 IMPORTANT

DO NOT use pipe dope or any pipe sealant on gas orifice 

threads.

6. 

Replace  the  gas  valve  regulator  spring  with  the 

provided regulator spring. See Figure 6.

7. 

A80 and 80G1 units with Nox inserts being converted 

from natural to LP /Propane.
a. 

Remove  the  burner  box  assembly  from  the 

vestibule panel.

b. 

Remove  the  screws  which  secure  each  of  the 

NOx  inserts  to  the  clamshell.  Remove  the  NOx 

inserts and reinstall the screws. See Figure 1.

c. 

Re-install burner box assembly.

NOx Insert

Re-install Screws

Figure 1. NOx Inserts

8.  Re-install the manifold/valve assembly.
9. 

Thread  provided  brass  fitting  to  gas  valve  inlet  until 

hand tight. Using properly sized wrench, tighten fitting 

2 to 3 full turns being careful to position the side port to 

allow clearance for the pressure switch and harness. 

See Figure 2.

NOTE: 

Never use channel lock pliers or a pipe wrench 

on the brass fitting.

NOTE: 

Some installations may require the pressure 

switch and fitting assembly to be positioned differently 

than shown in Figure 2.

10. 

Thread the gas supply to the brass fitting until hand 

tight.  Using  properly  sized  wrench  to  support  brass 

fitting, tighten supply line into fitting 2 to 3 full turns to 

achieve leak free joint.

NOTE: Do not over tighten. (Maximum 3 full turns past 

hand tight for ½” NPT per ASME B1.20.1-2013)

11. 

Thread  pressure  switch  to  brass  fitting  2  to  3  turns 

past hand tight, then wire as shown in Figure 7.

12. 

Restore the electrical power to the unit.

13.  Inspect all sides of assembly. Turn on gas supply. 

Immediately  check  the  entire  fitting  surface  and 

assembly joints for gas leaks.

14. 

Affix  nameplate  conversion  sticker  next  to  unit 

nameplate.

15.  Complete the information required on the gas converter 

sticker: date, name, and address. Affix sticker to the 

exterior of the unit in a visible area.

16. 

Follow the steps given in the start-up and adjustment 

section.

 IMPORTANT

Carefully check all piping connection for gas leaks. DO 

NOT use matches, candles, open flames or other means 

of ignition to check for gas leaks. Use a soap solution or 

other preferred means.

 CAUTION

Some soaps used for leak detection are corrosive to 

certain metals. Carefully rinse piping thoroughly after 

leak test has been completed. Do not use matches, 

candles, flame or other sources of ignition to check for 

gas leaks.

Brass Fitting

Low Inlet Pressure Switch

Figure 2. Gas Valve with Low Inlet Pressure Switch 

Location

Summary of Contents for 11K50

Page 1: ... is not proper and complete until the operation of the converted furnace is checked as specified in the furnace manufacturer s instructions supplied with the kit Shipping and Packing List Package 1 of 1 contains 12 Main burner orifices 0 034 1 Gas converter sticker 1 Nameplate conversion sticker 1 Bag assembly containing 1 Gas valve regulator spring 1 Low gas inlet pressure switch 1 Gas valve inle...

Page 2: ...ver use channel lock pliers or a pipe wrench on the brass fitting NOTE Some installations may require the pressure switch and fitting assembly to be positioned differently than shown in Figure 2 10 Thread the gas supply to the brass fitting until hand tight Using properly sized wrench to support brass fitting tighten supply line into fitting 2 to 3 full turns to achieve leak free joint NOTE Do not...

Page 3: ...re tor 5 Check the regulator setting ing the gas meter 6 Re install the barbed fiting Inlet Pressure Tap Pressure Regulator Adjusting Screw Spring LP Spring will be red Gas Inlet Barbed Fitting if equipped Figure 6 Conversion of Gas Valve GAS VALVE NO C WHITE ORANGE LOW INLET PRESSURE SWITCH YELLOW ORANGE PROVIDED HARNESS WIRES MV MV Figure 7 Low Inlet Pressure Switch Wiring Point to Point Wiring ...

Page 4: ... check gas orifices for proper size and restriction Remove temporary gas meter if installed Supply Pressure Measurement When testing supply gas pressure use the 1 8 N P T supply line tap located on the gas valve to facilitate test gauge connection See Figure 2 Check gas line pressure with unit firing at maximum rate Low pressure may result in erratic operation or underfire High pressure can result...

Reviews: