Save these instructions for future reference

INSTALLATION INSTRUCTIONS

Gas Changeover Kit

Natural to Regulated LP/Propane (Kit #11K50)

For A80, 80G1, A93, A95, 92G1, 95G1 and 96G1 Units

Manufactured By

Allied Air Enterprises LLC

A Lennox International, Inc. Company

215 Metropolitan Drive

West Columbia, SC 29170

This manual must be left with the homeowner for future reference.

 

(P) 507369-03

*P507369-03*

 WARNING

In the U.S., this conversion kit is to be installed by a licensed professional service technician (or equivalent) or other 

qualified agency in accordance with the manufacturer’s instructions and all codes and requirements of the authority having 

jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion, or production of carbon 

monoxide may result, causing property damage, personal injury or loss of life. The qualified agency is responsible for the 

proper installation of the kit. The installation is not proper and complete until the operation of the converted furnace is 

checked as specified in the furnace manufacturer’s instructions supplied with the kit.

Shipping and Packing List

Package 1 of 1 contains:

12 -Main burner orifices (0.034)

1 - Gas converter sticker
1 - Nameplate conversion sticker
1 - Bag assembly containing:

1- Gas valve regulator spring

1- Low gas inlet pressure switch
1- Gas valve inlet brass fitting

1- Wiring harness

Check the kit for shipping damage. If you find any damage, 

immediately contact the last carrier.

Application

Use natural to LP/Propane gas conversion kit 11K50 to 

convert units from natural gas to LP/Propane.

Installation

 CAUTION

As with any mechanical equipment, personal injury can 

result  from  contact  with  sharp  sheet  metal  edges.  Be 

careful when you handle this equipment.

 CAUTION

Gas valve conversion kit MUST be installed BEFORE 

the  unit  is  fired  using  LP/propane  gas.  Unit  damage 

WILL OCCUR if the unit is fired using LP/propane gas 

with the original natural gas orifices.

1. 

Set  the  thermostat  to  the  lowest  setting.  If  the  gas 

supply line has been connected, shut off the gas 

supply to the furnace, then disconnect the electrical 

power.

Summary of Contents for 11K50

Page 1: ... is not proper and complete until the operation of the converted furnace is checked as specified in the furnace manufacturer s instructions supplied with the kit Shipping and Packing List Package 1 of 1 contains 12 Main burner orifices 0 034 1 Gas converter sticker 1 Nameplate conversion sticker 1 Bag assembly containing 1 Gas valve regulator spring 1 Low gas inlet pressure switch 1 Gas valve inle...

Page 2: ...ver use channel lock pliers or a pipe wrench on the brass fitting NOTE Some installations may require the pressure switch and fitting assembly to be positioned differently than shown in Figure 2 10 Thread the gas supply to the brass fitting until hand tight Using properly sized wrench to support brass fitting tighten supply line into fitting 2 to 3 full turns to achieve leak free joint NOTE Do not...

Page 3: ...re tor 5 Check the regulator setting ing the gas meter 6 Re install the barbed fiting Inlet Pressure Tap Pressure Regulator Adjusting Screw Spring LP Spring will be red Gas Inlet Barbed Fitting if equipped Figure 6 Conversion of Gas Valve GAS VALVE NO C WHITE ORANGE LOW INLET PRESSURE SWITCH YELLOW ORANGE PROVIDED HARNESS WIRES MV MV Figure 7 Low Inlet Pressure Switch Wiring Point to Point Wiring ...

Page 4: ... check gas orifices for proper size and restriction Remove temporary gas meter if installed Supply Pressure Measurement When testing supply gas pressure use the 1 8 N P T supply line tap located on the gas valve to facilitate test gauge connection See Figure 2 Check gas line pressure with unit firing at maximum rate Low pressure may result in erratic operation or underfire High pressure can result...

Reviews: