Exhaust Requirements
35
70457901ENR7
Figure 19
NOTE: Do not install wire mesh or screen in
exhaust duct opening to avoid lint build-up or
impacting proper discharge of air from tumble
dryers.
NOTE: Where exhaust duct pierces a combustible
wall or ceiling, the opening must be sized per local
codes.
NOTE: Inside of duct must be smooth. Do not use
sheet metal screws to join sections.
Consult your local building code for regulations which
may also apply.
1
Removable strip of panel in framing wall to permit removal of tumble dryer from framing wall
2
Partition or bulkhead
3
Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm)
4
2 in. (51 mm) minimum clearance on both sides of duct
5
Exhaust airflow – maximum length of rigid duct 14 ft. (4.3 m) or 7.87 ft. (2.4 m) of flexible metal duct
TMB2361N
TMB2362N
TMB2360N