• Exhaust duct must not be connected to any other duct, vent, or

chimney.

• Dryer exhausts 220 cfm per unit (measured at back of dryer).
• DO NOT install flexible duct in concealed spaces, such as a

wall or ceiling.

• Static pressure in exhaust duct should not be greater than 0.6

inches water column [1.5 cm water column] , measured with
manometer placed on exhaust duct 2 feet [610 mm] from dry-
er (check with dryer running and no load).

• Exhausting dryer in hard-to-reach locations can be done by

installing 521P3 Flexible Metal Vent Kit (available as option-
al equipment at extra cost).

• Sufficient make-up air must be supplied to replace the air ex-

hausted by the dryer. The free area of any opening for outside
air must be at least 40 in.

2

 [25806 mm

2

] per unit.

• Failure to exhaust dryer properly will void warranty.
• A dryer will dissipate 60 Btu/ft

2

 [681,392 J/m

2

] of surface

area exposed to the conditioned air.

NOTE: Venting materials are not supplied with the dry-
er (obtain locally).

IMPORTANT: DO NOT block the airflow at the bottom of
the dryer’s front panel with laundry, rugs, etc. Blockage
will decrease airflow through the dryer, thus reducing
the efficiency of the dryer.

 Exhaust Direction

The dryer can be exhausted to the outdoors through the back, left,
right or bottom of the dryer. EXCEPTION: Gas dryers cannot be
vented out the left side because of the burner housing.

Dryer is shipped from factory ready for rear exhaust.

Exhausting the dryer through sides or bottom can be accomplish-
ed by installing a Directional Exhaust Kit, 528P3, available as
optional equipment at extra cost.

 Exhaust System

For best drying results, recommended maximum length of ex-
haust system is shown in 

Table 2 

.

To prevent backdraft when dryer is not in operation, outer end of
exhaust pipe must have a weather hood with hinged dampers (ob-
tain locally).

NOTE: Weather hood should be installed at least 12 in-
ches [305 mm] above the ground. Larger clearances
may be necessary for installations where heavy snow-
fall can occur.

Number of 90° Elbows

Weather Hood Type

Recommended

Use Only for Short Run Installations

D673I_SVG

1

1

1.   4 in. [102 mm]

D802I_SVG

1

1.   2.5 in. [64 mm]

Maximum length of 4 in. [102 mm] diameter rigid metal duct.

0

65 feet [19.8 m]

55 feet [16.8 m]

1

55 feet [16.8 m]

47 feet [14.3 m]

2

47 feet [14.3 m]

41 feet [12.5 m]

3

36 feet [11.0 m]

30 feet [9.1 m]

4

28 feet [8.5 m]

22 feet [6.7 m]

Table 2

NOTE: Deduct 6 feet [1.8 m] for each additional elbow.

Installation

©

 Copyright, Alliance Laundry Systems LLC -

 DO NOT COPY or TRANSMIT

  14

  Part No. D518518ENR1

Summary of Contents for Speed Queen DR5003WE

Page 1: ...r Dryers Original Instructions Keep These Instructions for Future Reference CAUTION Read the instructions before using the machine If this machine changes ownership this manual must accompany machine Part No D518518ENR1 April 2022 ...

Page 2: ......

Page 3: ...r user smells gas The gas utility instructions plus the SAFETY and WARNING note directly above must be posted in a prominent location near the dryer for customer use WARNING Installation of unit must be performed by a quali fied installer Install clothes dryer according to manufacturer s instructions and local codes DO NOT install a clothes dryer with flexible plas tic venting materials If flexibl...

Page 4: ...er or gas fitter This appliance must be installed with a 36 inch 910 mm long flexible gas connector A T Handle type gas shut off valve must be installed in the gas supply line to this appliance This appliance must not be installed in a bedroom or bath room Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 4 Part No D518518ENR1 ...

Page 5: ... with Three Wire Plug 17 Connecting Power Cord with Four Wire Plug 19 Reverse Door if Desired 20 Wipe Out Inside of Dryer 22 Plug In the Dryer 22 Electric Dryer 22 Gas Dryers 22 Grounding Information 23 Recheck Steps 23 Check Heat Source 23 Electric Dryers 24 Gas Dryers 24 Installer Checklist 25 Copyright 2021 Alliance Laundry Systems LLC All rights reserved No part of the contents of this book ma...

Page 6: ... 1035 mm E 42 75 in 1086 mm F 15 4 in 391 mm G 15 44 in 392 mm H 26 875 in 683 mm I 4 0 in 102 mm J 0 4 in 11 mm K 4 5 in 114 mm L 28 in 711 mm M 23 5 in 597 mm NOTE Exhaust openings are 4 inch 102 mm metal ducting With leveling legs turned into base Dimensions Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 6 Part No D518518ENR1 ...

Page 7: ... 75 in 1086 mm F 15 4 in 391 mm G 15 44 in 392 mm H 2 8 in 70 mm I 2 3 in 60 mm J 26 875 in 683 mm K 4 in 102 mm L 0 4 in 10 mm M 4 5 in 114 mm N 28 in 711 mm O 23 5 in 597 mm NOTE Exhaust openings are 4 inch 102 mm metal ducting With leveling legs turned into base Dimensions Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 7 Part No D518518ENR1 ...

Page 8: ...nect the gas supply pipe Check for gas leaks 5 For electric models only connect the electrical cord 6 Reverse the door if desired 7 Wipe out the inside of the dryer 8 Plug in the dryer 9 Recheck steps 10 Start and run the dryer in a heat setting to verify dryer is heat ing Position and Level the Dryer 1 Install dryer before washer This allows room for attaching exhaust duct 2 Select a location wit...

Page 9: ...1 Dryer Base 2 Level 3 Leveling Leg Figure 2 Installation Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 9 Part No D518518ENR1 ...

Page 10: ...e View Closet Door Front View Closet Door DRY2637N_SVG F F 2 G 1 Closet Door 2 Centered Air Openings G 2 Openings minimum 3 Outer Wall of Enclosure Figure 3 Installation Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 10 Part No D518518ENR1 ...

Page 11: ...t must be cleaned before installing the steam connection Turn on the water supply faucet and flush the line for approximately two minutes to remove any foreign materi als that could clog the screen in the water valve This is especial ly important when installing your steam dryer in a newly con structed or renovated building Build up may have occurred dur ing construction NOTE Y connector extension...

Page 12: ...ose Y Connector on Water Supply DRY2869N_SVG COLD HOT C H 4 9 8 5 6 7 10 1 2 3 2 3 1 Faucet 2 Filter Screen 3 Rubber Washer 4 Install this end to Y connector 5 Install this end to valve at rear of dryer 6 Water Fill Valve 7 Dryer Rear Panel 8 Washer Rear Panel 9 Inlet Hose 10 Extension Hose Figure 5 IMPORTANT Hoses and other rubber parts deteriorate after extend ed use Hoses may develop cracks bli...

Page 13: ...ed for a clothes dryer W048 WARNING Risk of fire Do not install a booster fan in the exhaust duct W1072 NOTE The booster fan warning does not apply to clothes dryers intended to be installed in a multiple clothes dryer system with an engineered exhaust duct system that is installed per the clothes dryer manufac turer s guidelines 1 Correct 2 Incorrect Figure 6 DO NOT use plastic thin foil or type ...

Page 14: ...dryer Exhaust Direction The dryer can be exhausted to the outdoors through the back left right or bottom of the dryer EXCEPTION Gas dryers cannot be vented out the left side because of the burner housing Dryer is shipped from factory ready for rear exhaust Exhausting the dryer through sides or bottom can be accomplish ed by installing a Directional Exhaust Kit 528P3 available as optional equipment...

Page 15: ...m 5 0 inch water column pressure to maximum 10 5 inch water column pressure For proper operation at altitudes above 3000 feet 915 m the nat ural gas valve spud orifice size must be reduced to ensure com plete combustion Refer to Table 3 Natural Gas Altitude Adjustments Altitude Orifice Size Part No feet m No inches mm 3000 915 43 0 0890 2 26 D503778 6000 1830 44 0 0860 2 18 58719 8000 2440 45 0 08...

Page 16: ...5 0 0520 1 32 58755 8000 2440 56 0 0465 1 18 D503786 Table 4 Connect Electrical Plug Electric Dryer Only Dryer requires 120 240 Volt or 120 208 Volt 60 Hertz 3 or 4 wire electrical supply Refer to serial plate for specific electrical requirements IMPORTANT Use only a new U L listed No 10 copper wire only three or four conductor power supply cord kit rated 240 Volts minimum 30 Amperes and labeled a...

Page 17: ... 208 Volt NOTE Branch circuit wire size requirements to laundry room outlet are shown in table below Wire Length Wire Less than 15 ft 4 5 m Listed No 10 AWG Copper wire only Table 5 continues Wire Length Wire Longer than 15 ft 4 5 m Listed No 8 AWG Copper wire only Table 5 The power cord connection between wall receptacle and dryer terminal block IS NOT supplied with dryer Type of power cord and g...

Page 18: ...ce Entrance Switch Box Refer to NOTE above 8 30 Ampere Fuses or Circuit Breaker 9 Neutral Wire 10 Metallic or Non Metallic Sheathed Cable Copper Wire Only 11 Power Cord Not supplied with dryer 12 Neutral 13 Terminal Block in Dryer 14 Intermediate Shut Off Box may or may not be fused 15 Direct Connection 16 Power Cord Connection Figure 8 1 Disconnect power to dryer 2 Remove access cover from rear o...

Page 19: ...able indicating device connected to the center earth ground pin of the plug and the green screw on the back of the cabinet 8 Reinstall access cover and screw Connecting Power Cord with Four Wire Plug NOTE Four wire cord is required for new branch cir cuit installations mobile homes or where codes do not permit grounding through neutral DRY2016N_SVG 7 7 7 7 6 3 2 1 4 5 1 Typical Four Wire Receptacl...

Page 20: ...nstalling the white wire loop the free eyelet end of the earth ground to neutral wire re moved in Step 3 and attach along with the white wire to the neutral center terminal on the terminal block 7 Using a screwdriver tighten all screws firmly IMPORTANT Failure to tighten these screws firmly may result in wire failure at the terminal block 8 Secure the strain relief to the power cord or wires where...

Page 21: ...r panel DRY1916N_SVG B A Figure 19 4 Rotate door panel 180 degrees as shown D273P_SVG Figure 20 5 Remove door strike from door liner and reinstall on opposite side DRY1917N_SVG Figure 21 6 Insert liner under flange on bottom of door then push top of door liner into place DRY1918N_SVG B A Figure 22 7 Reinstall nine screws removed in Step 2 DRY1919N_SVG Figure 23 Installation Copyright Alliance Laun...

Page 22: ...ectrical power source Refer to Electric Dryer Only Connect Electrical Plug for information on con necting power cord Connect to 30 Amp circuit D275I_SVG 3 2 1 4 Figure 27 Gas Dryers Dryer requires 120 Volt 60 Hertz electrical supply and comes equipped with a 3 prong grounding plug Refer to serial plate for specific electrical requirements NOTE The wiring diagram is located in the control hood WARN...

Page 23: ...tection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or re move the grounding prong from this plug W036 WARNING Improper connection of the equipment grounding conductor can result in a risk of electric shock Check with a qualified electrician or service person if you are in doubt as to whether the dryer is properly grounded W038 Do ...

Page 24: ...d for approximately five minutes observe burner flame through lower front panel 4 Adjust the air shutter to obtain a soft uniform blue flame A lazy yellow tipped flame indicates lack of air A harsh roar ing very blue flame indicates too much air Adjust the air shutter as follows a Loosen the air shutter lockscrew b Turn the air shutter to the left to get a luminous yellow tipped flame then turn it...

Page 25: ...ECK CHECK 3 Connect Dryer Ex haust System 8 Plug In the Dryer Electric D275I_SVG1 Gas TLW2289N_SVG CHECK CHECK 4 GAS ONLY Connect Gas Sup ply Pipe Check for Gas Leaks 9 Recheck Steps CHECK CHECK 5 ELECTRIC ONLY Connect Electrical Cord D699I_SVG1 10 Start and Run Dryer in Heat Setting to Verify Dryer is Heating CHECK CHECK Refer to the manual for more detailed information Installer Checklist Copyri...

Reviews: