47
and leave a proper space.
No power supply wire is provided; please refer to the requirements of na
ti
onal standards or factory.
In the following table, power supply wire and connec
ti
on length
are specified to keep voltage drop
within 2%. If wire con
ti
nuous length exceeds the ones listed in the table, please choose wires with the
right diameters according to rela
ti
ve regula
ti
on.
W
hen fi
nishing wiring
, first carry out a careful inspection of connections before switching on.
ALLWH200R410
Power supply
380-415V, 3Ph, 50Hz
Min. wire size
(metal pipe & synthetic resin pipe wire)
Wire size (˂30m)
6mm
2
Ground wire
4mm
2
Manual switch
Capacity
50A
Fuse
30 A
Leakage protector
30mA 0.1sec below
ALLWH420R410
Power supply
380-415V, 3Ph, 50Hz
Min. wire size
(metal pipe & synthetic resin pipe wire)
Wire size (˂30m)
10# (UL1015)
Ground wire
10# (UL1015)
Manual switch
Capacity
63 A
Fuse
50 A
Leakage protector
30mA 0.1sec below
ALLWH800R410
Power supply
380-415V, 3Ph, 50Hz
Min. wire size
(metal pipe & synthetic resin pipe wire)
Wire size (˂30m)
25mm
2
Ground wire
25mm
2
Manual switch
Capacity
125A
Fuse
100A
Leakage protector
30mA 0.1sec below
$OOLDQFHR410A Direct Heating Type HPWH 50Hz Technical Manual MCAC-HTSM-201801