Area
Description
Free Standing/Alcove In-
stallation
Closet Installation
A*
Dryer sides and rear clearance
0 mm [0 in.]
0 mm [0 in.]
B
Dryer top clearance
305 mm [12 in.]
305 mm [12 in.]
C
Dryer front clearance
Not Applicable
51 mm [2 in.]
D
Exhaust duct clearance to com-
bustible material
51 mm [2 in.]
51 mm [2 in.]
E
Weather hood to ground clear-
ance
305 mm [12 in.]
305 mm [12 in.]
F
Distance from floor or ceiling
to air opening edge
Not Applicable
76 mm [3 in.]
G
Area of centered air openings
in closet door. Louvered door
with equivalent air openings is
acceptable. (Minimum clearan-
ces are shown.)
Not Applicable
1016 sq. mm/open [40 sq. in./
open]
H
For new installations, it is sug-
gested to locate top of wall vent
1067 mm [42 inches] above
floor to make venting easier to
connect.
1067 mm [42 in.]
1067 mm [42 in.]
*
Rear clearance is minimum. 51 mm [2 inches] is recommended for utility connection. 152 mm [6
inches] is recommended when venting through rear of unit.
Table 1
IMPORTANT: In mobile home installations, gas dryers
MUST be permanently attached to the floor at the time
of installation. Order No. 526P3 Hold Down Kit (availa-
ble at extra cost) for a manufactured (mobile) home in-
stallation. Follow the instructions supplied with the kit.
Connect Dryer Exhaust System
WARNING
To reduce the risk of fire and combustion gas accu-
mulation the dryer MUST be exhausted to the out-
doors.
W604
WARNING
To reduce the risk of fire and the accumulation of
combustion gases, DO NOT exhaust dryer air into a
window well, gas vent, chimney or enclosed, unven-
tilated area, such as an attic, wall, ceiling, crawl
space under a building or concealed space of a
building.
W045
WARNING
To reduce the risk of fire, DO NOT use plastic or thin
foil ducting to exhaust the dryer.
W354
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
10
Part No. D516105R2