Alliance Laundry Systems 506126R5 Installation Instructions Manual Download Page 10

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

506126

10

4. Tighten all connections securely. Turn on gas and 

check all pipe connections (internal & external) 

for gas leaks with a non-corrosive leak detection 

fluid. 

NOTE: The dryer and its appliance main gas valve 

must be disconnected from the gas supply piping 

system during any pressure testing of that system 

at test pressures in excess of 1/2 psi (3.45 kPa). 

Refer to 

Step 9 (Check Heat Source)

.

L.P. (Liquefied Petroleum) Gas

, 2500 Btu/ft

3

 

(93.1 MJ/m

3

) service must be supplied at 10 ± 1.5 inch 

water column pressure.
For proper operation at altitudes above 2500 feet (760 m) 

the L.P. gas valve spud orifice size must be reduced to 

ensure complete combustion. Refer to 

Table 3

.

NOTE: DO NOT connect the dryer to L.P. Gas 

Service without converting the gas valve. Install 

L.P. Gas Conversion Kit 649P3, available at extra 

cost.

Step 4: (Electric Dryer Only) Connect 
Electrical Plug

Dryer requires 120/240 Volt or 120/208 Volt, 60 Hertz, 

3 wire electrical suppy. Refer to serial plate for 

specific electrical requirements.

IMPORTANT: Use only a new U.L. listed No. 10 

(copper wire only) three or four conductor power 

supply cord kit rated 240 Volts (minimum) 30 

Amperes and labeled as suitable for use in a clothes 

dryer.

NOTE: The wiring diagram is located behind the 

control panel, inside the control cabinet.

Grounding Information

This appliance must be grounded. In the event of 

malfunction or breakdown, grounding will reduce the 

risk of electric shock by providing a path of least 

resistance for electric current. The cord-kit must be 

equipped with a cord having an equipment-grounding 

conductor and a grounding plug. The plug must be 

plugged into an appropriate outlet that is properly 

installed and grounded in accordance with all local 

codes and ordinances.

Do not modify the plug provided with the cord-kit - if 

it will not fit the outlet, have a proper outlet installed 

by a qualified electrician. 

L.P. Altitude Adjustments

Altitude

Orifice Size

Part No.

feet

m

No.

inches

mm

3000

915

55

0.0520

1.32

58755

8000

2440

56

0.0465

1.18

503786

Table 3 

To reduce the risk of fire, electric shock, 

serious injury or death, all wiring and 

grounding MUST conform with the latest 

edition of the National Electrical Code, 

ANSI/NFPA 70, or the Canadian Electrical 

Code, CSA C22.1, and such local 

regulations as might apply. It is the 

customer’s responsibility to have the wiring 

and fuses installed by a qualified electrician 

to make sure adequate electrical power is 

available to the dryer.

W521

WARNING

Improper connection of the equipment-

grounding conductor can result in a risk of 

electric shock. Check with a qualified 

electrician or service person if you are in 

doubt as to whether the dryer is properly 

grounded.

W038

WARNING

Summary of Contents for 506126R5

Page 1: ...w comlaundry com Installation Instructions for Front Control Dryers Dimensions 3 Before You Start 4 Installing the Dryer 5 Installer Checklist Back Cover Date Purchased __________________________ Mode...

Page 2: ...er s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier W052 FOR YOUR SA...

Page 3: ...6 cm 4 0 in 10 2 cm 26 9 in 68 3 cm ELECTRIC DRYERS 8 0 in 20 3 cm 15 4 in 39 1 cm 15 44 in 39 2 cm 37 44 in 95 1 cm DRY2282N With leveling legs turned into base 1 3 8 in NPT Gas Connection DRY2282N...

Page 4: ...u Start Supplies For most installations the basic supplies you will need are Figure 1 D818I 1 Wrench 2 Screwdriver 3 Level 4 Duct Tape 5 Teflon Tape Gas Models 1 2 3 5 4 Any disassembly requiring the...

Page 5: ...tion and for easier installation and servicing Minimum clearances are shown below Figure 2 DRY1914N NOTE For new installations locate top of wall vent 42 inches 106 7 cm above floor to make venting ea...

Page 6: ...e dryer Use as few elbows as possible DRY2345N 1 Dryer Base 2 Level 3 Leveling Leg 1 2 3 A clothes dryer produces combustible lint To reduce the risk of fire and combustion gas accumulation the dryer...

Page 7: ...secured to mobile home structure Dryer exhaust duct MUST NOT terminate under mobile home Exhaust duct must not be connected to any other duct vent or chimney Dryer exhausts 220 cfm measured at back of...

Page 8: ...in operation outer end of exhaust pipe must have a weather hood with hinged dampers obtain locally NOTE Weather hood should be installed at least 12 inches 30 5 cm above the ground Larger clearances...

Page 9: ...in NPT pipe plug must be installed as shown for checking inlet pressure Refer to Figure 5 To reduce the risk of gas leaks fire or explosion The dryer must be connected to the type of gas as shown on...

Page 10: ...ram is located behind the control panel inside the control cabinet Grounding Information This appliance must be grounded In the event of malfunction or breakdown grounding will reduce the risk of elec...

Page 11: ...Do not connect dryer to 110 115 or 120 Volt circuit Heating elements are available for field installation in dryers which are to be connected to electrical service of different voltage than that list...

Page 12: ...30 Ampere Fuses or Circuit Breaker 6 Neutral 3 Neutral Wire 7 Terminal Block in Dryer NOTE The power cord is NOT supplied with the electric dryer Type of power cord and gauge of wire must conform to l...

Page 13: ...n before plugging the cord into an outlet Use an acceptable indicating device connected to the center grounding pin of the plug and the green screw on the back of the cabinet 8 Reinstall access cover...

Page 14: ...ws a Red wire to L1 terminal b Black wire to L2 terminal c White wire to Neutral terminal NOTE When installing the white wire loop the free eyelet end of the ground wire removed in Step 4 and attach a...

Page 15: ...t then pull down removing door liner from door panel 4 Rotate door panel 180 degrees as shown 5 Remove door strike from door liner and reinstall on opposite side 6 Insert liner under flange on bottom...

Page 16: ...operate both a washer and gas dryer on the same circuit Use separetely fused 15 amp circuits The dryer is designed to be operated on a separate branch polarized three wire effectively grounded 120 Vo...

Page 17: ...e problem Do not operate other appliances on the same circuit when this appliance is operating Step 8 Recheck Steps 1 7 Refer to Installer Checklist on the back cover of this manual and make sure that...

Page 18: ...to obtain a soft uniform blue flame A lazy yellow tipped flame indicates lack of air A harsh roaring very blue flame indicates too much air Adjust the air shutter as follows 1 Loosen the air shutter l...

Page 19: ......

Page 20: ...EVEL D255I D255I 2 DRY688N Connect Dryer Exhaust System CHECK DRY688N 3 GAS ONLY D258I CHECK Connect Gas Supply Pipe Check for Gas Leaks 4 D699IE0A ELECTRIC ONLY Connect Electrical Cord CHECK D699IE0A...

Reviews: