Electrical Requirements
M414905
46
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
50 and 75 Pound Electric Models
Refer to
.
NOTE: Wire size and breaker ratings were
obtained from the Canadian Electrical Code for
75 C. wire and are intended for use as a guideline
only. Electrical connections should be made by a
qualified electrical contractor in accordance with
all applicable local and national requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
Serial Plate Rating
Terminal Block
Connections
Required
Serial Plate Amps
Recommended Circuit
Nonreversing
Reversing
Breaker
Rating
Wire Size
AWG (mm
2
)
240V/50Hz/1ph
(50 Pound only)
L1, Neutral and Ground
93
95
125A – 1 pole
1 (42.4)
200-208V/60Hz/3ph
L1, L2, L3 and ground
89
88
125A – 3 pole
1 (42.4)
200V/50Hz/3ph
L1, L2, L3 and ground
84
85
125A – 3 pole
1 (42.4)
230V/50Hz/3ph
L1, L2, L3 and ground
73
75
100A – 3 pole
3 (26.7)
240V/50Hz/3ph
L1, L2, L3 and ground
79
78
100A – 3 pole
3 (26.7)
240V/60Hz/3ph
L1, L2, L3 and ground
79
78
100A – 3 pole
3 (26.7)
380V/50 or 60Hz/3ph
L1, L2, L3 and ground
47
48
60A – 3 pole
6 (13.3)
400-415V/50Hz/3ph
L1, L2, L3 and ground
43
44
60A – 3 pole
6 (13.3)
440V/60Hz/3ph
L1, L2, L3 and ground
41
41
51A – 3 pole
6 (13.3)
480V/60Hz/3ph
L1, L2, L3 and ground
38
38
50A – 3 pole
6 (13.3)
Table 9