System Installation Recommendations
Preventing Excessive Heat
For most applications, normal convection cooling will keep the SLC 500
controller components within the specified operating range of 0 °C...60 °C
(32 °F...140 °F). Proper spacing of components within the enclosure is usually
sufficient for heat dissipation.
In some applications, a substantial amount of heat is produced by other
equipment inside or outside the enclosure. In this case, place blower fans
inside the enclosure to assist in air circulation and to reduce hot spots near the
SLC 500 controller.
Additional cooling provisions might be necessary when high ambient
temperatures are encountered.
IMPORTANT
Do not bring in unfiltered outside air. It may introduce harmful
contaminants of dirt that could cause improper operation or
damage to components. In extreme cases, you may need to use
air conditioning to protect against heat build-up within the
enclosure.
Summary of Contents for SLC 500
Page 4: ...Publication 1747 UM011G EN P June 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1747 UM011G EN P June 2008 12 Table of Contents Glossary Index ...
Page 26: ...Publication 1747 UM011G EN P June 2008 26 Quick Start for Experienced Users Notes ...
Page 54: ...Publication 1747 UM011G EN P June 2008 54 Selecting Your Hardware Components Notes ...
Page 74: ...Publication 1747 UM011G EN P June 2008 74 System Installation Recommendations Notes ...
Page 110: ...Publication 1747 UM011G EN P June 2008 110 Installing Your Hardware Components Notes ...
Page 168: ...Publication 1747 UM011G EN P June 2008 168 Troubleshooting Notes ...
Page 174: ...Publication 1747 UM011G EN P June 2008 174 Replacement Parts Notes ...
Page 180: ...Publication 1747 UM011G EN P June 2008 180 Specifications ...
Page 200: ...Publication 1747 UM011G EN P June 2008 200 Setting Up the DH 485 Network Notes ...
Page 286: ...Publication 1747 UM011G EN P June 2008 286 Glossary Notes ...