Publication 1747-UM011G-EN-P - June 2008
178
Specifications
CPU hold-up time
(4)
20 ms (full load)
3000 ms (no load)
5 ms (full load)
1000 ms (no load)
20 ms (full load)
3000 ms (no load)
Certification
(when product is marked)
UL Listed Industrial Control Equipment for Class I,
Division 2, Groups A, B, C, D Hazardous Locations
UL Listed Industrial Control
Equipment
C-UL Listed Industrial Control Equipment for Class I,
Division 2,
Groups A, B, C, D Hazardous Locations
CSA Certified Process Control
Equipment for
Class I, Div 2, Groups A, B, C,
D Hazardous Locations
CE
(7)
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2 Industrial Immunity
EN 50081-2 Industrial Emissions
or
EN 61000-6-2 Industrial Immunity
EN 61000-6-4 Industrial Emissions
European Union 73/23/EEC LVD Directive, compliant with safety related portions of:
EN61131-2 Programmable Controllers
C-Tick, Australian Radio Communications Act, compliant with:
AS/NZS 2064 Industrial Emissions
(1)
Power supply fuse is to guard against fire hazard due to short-circuit conditions. Fuse may not protect the supply from miswiring or excessive transient in the power line.
(2)
Use time-delay type overcurrent protection in all ungrounded conductors.
(3)
Isolation is between input terminals and backplane.
(4)
CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.
(5)
Fuse sizes specified are for end-devices only. Fuse size may need to be reduced depending on the size of circuit wiring.
(6)
Equivalent fuses: 250V-3A fuse, nagasawa ULCS-61ML-3, or BUSSMAN AGC 3.
(7)
See the Product Certification link at
http://ab.com for Declarations of Conformity, Certificates, and other certification details.
(8)
Equivalent fuse: 250V-3A fuse, SANO SOC SD4, or BUSSMAN AGC 3.
(9)
Equivalent fuse: 125V-5A fuse, LITTLEFUSE 223.
(10)
The combination of all output power (5 volt backplane, 24 volt backplane, and 24 volt user source) cannot exceed 70 watts.
Attribute
Value
1746-P1
1746-P2
1746-P3
1746-P4
Summary of Contents for SLC 500
Page 4: ...Publication 1747 UM011G EN P June 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1747 UM011G EN P June 2008 12 Table of Contents Glossary Index ...
Page 26: ...Publication 1747 UM011G EN P June 2008 26 Quick Start for Experienced Users Notes ...
Page 54: ...Publication 1747 UM011G EN P June 2008 54 Selecting Your Hardware Components Notes ...
Page 74: ...Publication 1747 UM011G EN P June 2008 74 System Installation Recommendations Notes ...
Page 110: ...Publication 1747 UM011G EN P June 2008 110 Installing Your Hardware Components Notes ...
Page 168: ...Publication 1747 UM011G EN P June 2008 168 Troubleshooting Notes ...
Page 174: ...Publication 1747 UM011G EN P June 2008 174 Replacement Parts Notes ...
Page 180: ...Publication 1747 UM011G EN P June 2008 180 Specifications ...
Page 200: ...Publication 1747 UM011G EN P June 2008 200 Setting Up the DH 485 Network Notes ...
Page 286: ...Publication 1747 UM011G EN P June 2008 286 Glossary Notes ...