10–8
Troubleshooting
Publication 1747-6.2
The Following
Error Exists
Probable Cause
Recommended Action
System does
not operate per
programmed
forces.
User Programmed
Forces are Not
Enabled
1. Monitor program file online and identify programmed
forces.
2. Enable appropriate forces and test system conditions
again. Once forces are enabled, the FORCED I/O LED
goes on steady.
Refer to either the Hand-Held Terminal User Manual
(Catalog Number 1747-NP002) or your programming
software user manual.
The Following
Error Exists
Probable Cause
Recommended Action
CPU Major
Error with Low
or No Battery
Back-up
Loss of RAM
during Power
Down Period
1. Verify battery is connected. See pages 6–1 and 9–4.
2. Replace the battery if you want RAM battery backup.
See page 9–4. If you want to back up RAM with the
capacitor in a SLC 5/01 (1747-L511), add or replace the
BATTERY LOW LED jumper.
3. Refer to processor major fault recommended action
steps.
Refer to either the Hand-Held Terminal User Manual
(Catalog Number 1747-NP002) or your programming
software user manual.