PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Appendix
A
Supplemental Drive Information
Specifications
Unless otherwise noted, the following specifications pertain to drives
equipped with 700 Vector Control or 700S Phase II Control.
Topic
Page
Fuse and Circuit Breaker Ratings
Category
Specification
Frame 2
Frames 3A and 3B
Agency
Certification
Listed to UL508C and CAN/CSA-C2.2 No. 14-05. UL Listing for Frame 2 is applicable up to 480V AC. UL Listing for
Frame 3A and 3B is applicable up to 600V AC.
Marked for all applicable European Directives
(1)
EMC Directive (89/336/EEC)
EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations
Certified to AS/NZS, 1997 Group 1, Class A.
These drives are also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive
Systems.
IEC 146 - International Electrical Code.
CMAA Specification #70 (Crane Manufacturers of America Association)
(1)
Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.
U
c
U
S
L
®
N223
Category
Specification
Frame 2
Frames 3A and 3B
Protection 400V
480V
400V
480V
600V
690V
AC Input Overvoltage Trip:
528V AC
528V AC
528V AC
528V AC
760V AC
760V AC
AC Input Undervoltage Trip:
340V AC
340V AC
340V AC
340V AC
340V AC
340V AC
Bus Overvoltage Trip:
815V DC
815V DC
815V DC
815V DC
1168V DC 1168V DC
Bus Undervoltage Shutoff/Fault: 300V DC
300V DC
300V DC
300V DC
300V DC
300V DC
Nominal Bus Voltage:
600V DC
700V DC
600V DC
700V DC
900V DC
1000V DC
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
200% of rated current (typical)
220…300% of rated current (dependent on drive rating)
Line Transients:
Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity:
Showering arc transients up to 1500V peak
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182