background image

Publication 20A-IN010B-EN-P

The PowerFlex 70 drive contains protective MOVs and Common Mode 
Capacitors referenced to ground (see below). To guard against unstable 
operation and/or damage, the drive must be properly configured as shown in 

Table A on page 2

.

Important: All PowerFlex 70 drives are shipped with the DC bus common 

mode capacitors referenced to ground.

The information in this document supersedes the MOV and Common Mode 
Capacitor material in the following:

For additional general information, refer to:

Before proceeding, ensure that all power to the drive has been removed.

Title

Publication

PowerFlex 70 User Manual

20A-UM001M

PowerFlex 70 Installation Instructions

20A-IN009B

Title

Publication

Available Online at …

PowerFlex 70 User Manual

20A-UM001

www.rockwellautomation.com/
literature

Wiring and Grounding Guidelines for PWM AC Drives DRIVES-IN001
Guarding Against Electrostatic Damage

8000-4.5.2

!

ATTENTION:  This drive contains ESD (Electrostatic Discharge) 
sensitive parts and assemblies. Static control precautions are required 
when installing, testing, servicing or repairing this assembly. 
Component damage may result if ESD control procedures are not 
followed. If you are not familiar with static control procedures, 
reference A-B publication 8000-4.5.2, “Guarding Against 
Electrostatic Damage” or any other applicable ESD protection guide.

R/L1

S/L2

T/L3

DC+

DC–

MOV and AC EMI Capacitor Phase to Ground

Common Mode Capacitor to Ground

Jumper-Wire

Jumper-Wire

PowerFlex 70 Power Jumpers

Installation Instructions