PowerFlex 70 Power Jumpers
Jumper Settings and Locations
Fra
m
e
Vo
lt
ag
e
Code
Factory Default Jumper Settings
Power Source Type
MOV/Input Filter
Caps
DC Bus Common
Mode Caps
A
B
C
D
E
JP2/JP3
Installed
Not Applicable
Solid Ground
Insert jumper at the “JP2/JP3” location.
Non-Solid Ground
Remove the jumper at “JP2/JP3.”
B
B
C
D
E
JP2/JP3
Installed
JP5/JP6
Installed
Important: The Internal EMC Filter (input filter)
is a factory installed option on Frame B drives. If
the option is installed, the drive cannot be used
on a non-solid ground power source.
To verify: an extra “R, S, T” terminal block will be
present if the option is installed (as shown).
Additionally, the 13th character of the nameplate
catalog number will be an “A” (see
).
Solid Ground
Jumpers should be installed at both locations
(JP2/JP3 and JP5/JP6).
Non-Solid Ground
Remove the jumpers at “JP2/JP3” and “JP5/
JP6.” In addition, verify that the Input Filter
option is not installed.
C
B
C
D
E
JP2/JP3
Installed
JP3A/JP3B
Installed
Solid Ground
Jumpers should be installed at both locations
(JP2/JP3 and JP3A/JP3B).
Non-Solid Ground
Remove the jumpers at “JP2/JP3” and “JP3A/
JP3B.”
JP3
JP2
MOV
JP3
JP2
JP5
JP6
MOV
CM Cap
L1
R
L2
S
L3
T
BR1
+DC
L1
R
L2
S
L3
T
Input Filter
Option
JP6
JP5
JP3
JP2
MOV
CM Cap
L1
R
L2
S
L3
T
BR1
+DC
L1
R
L2
S
L3
T
Input Filter
Option
or
JP3
JP2
JP3A
JP3B
MOV / Filter Cap
CM Cap