7-6
Troubleshooting
Events
Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
Code
Event
Description
1
No Event
Empty event queue entry.
2
DPI Bus Off
Flt
A bus-off condition was detected on DPI. This event may be
caused by loose or broken cables or by noise.
3
Ping Time Flt A ping message was not received on DPI within the specified
time.
4
Port ID Flt
The adapter is not connected to a correct port on a DPI product.
5
Port Change
Flt
The DPI port changed.
6
Host Sent
Reset
The DPI product issued this because it was reset.
7
EEPROM
Sum Flt
The EEPROM in the adapter is corrupt.
8
Online @
125kbps
The adapter and DPI product are communicating at 125kbps.
9
Online @
500kbps
The adapter and DPI product are communicating at 500kbps.
10
Bad Host Flt
The adapter was connected to an incompatible product.
11
Dup. Port Flt
Another peripheral with the same port number is already in use.
12
Type 0 Login
The adapter has logged in for type 0 control.
13
Type 0 Time
Flt
The adapter has not received a type 0 status message within
the specified time.
14
DL Login
The adapter has logged into a datalink.
15
DL Reject Flt The host rejected an attempt to log in to a datalink because the
datalink is not supported or is used by another peripheral.
16
DL Time Flt
The adapter has not received a datalink message within the
specified time.
17
Control
Disabled
The adapter has sent a “Soft Control Disable” command to the
DPI product.
18
Control
Enabled
The adapter has sent a “Soft Control Enable” command to the
DPI product.
19
Message
Timeout
A Client-Server message sent by the peripheral was not
completed.
20
DPI Fault Msg The Host faulted.
21
DPI Fault
Clear
The user cleared a fault in the adapter.
22
Normal
Startup
Peripheral completes a normal startup.
23
NET Comm
Flt
The adapter detected a fault condition on the PROFIBUS
network.
24
Fault Cfg
Error
One of the Flt Cfg data Parameters is set to a value greater than
65535 and the host requires a 16-bit value.
25
P-DP Online
The PROFIBUS adapter has gone on-line the PROFIBUS
network.
20COMM-UM006A-EN-P.book Page 6 Friday, September 28, 2001 10:43 AM
Summary of Contents for PowerFlex 20-COMM-P
Page 8: ...P 4 About This Manual 20COMM UM006A EN P book Page 4 Friday September 28 2001 10 43 AM...
Page 22: ...2 8 Installing the Adapter 20COMM UM006A EN P book Page 8 Friday September 28 2001 10 43 AM...
Page 30: ...3 8 Configuring the Adapter 20COMM UM006A EN P book Page 8 Friday September 28 2001 10 43 AM...
Page 94: ...7 8 Troubleshooting 20COMM UM006A EN P book Page 8 Friday September 28 2001 10 43 AM...
Page 101: ...Adapter Parameters B 5 Notes 20COMM UM006A EN P book Page 5 Friday September 28 2001 10 43 AM...
Page 102: ...B 6 Adapter Parameters 20COMM UM006A EN P book Page 6 Friday September 28 2001 10 43 AM...
Page 112: ...20COMM UM006A EN P book Page 2 Friday September 28 2001 10 43 AM...