4-2
Configuring the Scanner
For the scanner to communicate with a drive, the scanner must be
configured and the drive’s node number must be added to its scan list.
1.
Go online with RSNetWorx for DeviceNet. Refer to the
. The devices on the
network are displayed in the configuration view.
Figure 4.2 Configuration View (Graph)
2.
Right-click the DeviceNet scanner (node 00 in
) and select
Properties
. The Scanner Module dialog box appears.
Important:
If your scanner is an unrecognized device, you must
create an EDS file for it and then configure it. Create an
EDS file by following the instructions in the
Configure the scanner using the General and Module
tabs. Click
Help
or refer to your scanner documentation
if you need more information.
3.
Click the
Scanlist
tab. A message box prompts you to upload.
4.
Click
Upload
. Data is uploaded from the scanner, and then the
) appears.
5.
Select the
Automap on Add
box (a check mark will appear).
Setting Up the Scan List