POINT I/O 2 and 4 Relay Output Modules
17
Publication 1734-IN055H-EN-E - August 2016
Wire with AC Modules
ATTENTION:
The power supply voltage may be daisychained from a 1734
adapter, 1734-FPD or 1734-EP24DC communication interface. Each channel is
individually isolated and may have a unique supply and/or voltage as necessary.
ATTENTION:
Do not attempt to increase load current or wattage capability
beyond the maximum rating by connecting two or more outputs in parallel. The
slightest variation in relay switching time may cause one relay to momentarily
switch the total load current.
ATTENTION:
Make sure that all relay wiring is properly connected before
applying any power to the module.
ATTENTION:
Total current draw through the wiring base unit is limited to 10 A.
Separate power connections to the terminal base unit may be necessary.
ATTENTION:
Use the end cap from your adapter or interface module to cover
the exposed interconnections on the last mounting base on the DIN rail. Failure
to do so could result in equipment damage or injury from electric shock.