Allen-Bradley POINT I/O EtherNet/IP 1734-AENT Installation Instructions Manual Download Page 15

POINT I/O EtherNet/IP Adapter        

15

Publication  1734-IN590A-EN-P - March 2003

Environmental Conditions

Operational 
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

 

-20 to 55

°

C (-4 to 131

°

F)

Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating 

Cold),

 

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry 
Heat),

 

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating 
Thermal Shock): -40 to 85

°

C (-40 to 185

°

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating 
Damp Heat): 5 to 95% noncondensing

Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

Operating

30g peak acceleration

Nonoperating

50g peak acceleration

Vibration

IEC 60068-2-6 (Test Fc, Operating)

 

Tested 5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:

 

4kV contact discharges

 

8kV air discharges

Radiated RF Immunity IEC 61000-4-3:

 

10V/m with 1kHz sine-wave 80%AM from 30MHz to 
2000MHz

 

10V/m with 200Hz 50% pulse 100%AM from 900MHz

EFT/B Immunity

IEC 61000-4-4:

 

+4kV at 2.5kHz on power ports

 

+2kV at 5.0kHz on signal ports

Surge Transient 
Immunity

IEC 61000-4-5:

 

+1kV line-line(DM) and +2kV line-earth(CM) on signal 
ports

 

+1kV line-line(DM) and +2kV line-earth(CM) on power 
ports

Conducted RF 
Immunity

IEC 61000-4-6:

 

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 
80MHz

Emissions

CISPR 11

 

Group 1, Class A

Enclosure Type Rating

None (open-style)

Allen-Bradley

Summary of Contents for POINT I/O EtherNet/IP 1734-AENT

Page 1: ...herNet Network RJ45 Connector 5 System Power and Field Power Indicators 2 Network Address Thumbwheel 6 RTB Removal Handle 3 Indicators Adapter Status PointBus Status Network Activity and Network Statu...

Page 2: ...d with any particular installation Rockwell Automation does not assume responsibility or liability to include intellectual property liability for actual use based upon the examples shown in this publi...

Page 3: ...sion in a hazardous environment which may lead to personal injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can lead to personal...

Page 4: ...ed within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to...

Page 5: ...ilable use a static safe workstation When not in use store the equipment in appropriate static safe packaging ATTENTION POINT I O is grounded through the DIN rail to chassis ground Use zinc plated yel...

Page 6: ...ress thumbwheel 4 Slide the safety end cap up to remove This exposes the backplane and power interconnections WARNING If you connect or disconnect the EtherNet cable with power applied to this module...

Page 7: ...resents the number set on the switches The adapter s subnet mask will be 255 255 255 0 and the gateway address is set to 0 0 0 0 The adapter will not have a host name assigned or use any Domain Name S...

Page 8: ...he replacement adapter vertically above the DIN rail Make certain the DIN rail lock is in the horizontal position Slide the adapter down allowing the interlocking side pieces to engage the adjacent mo...

Page 9: ...on V Supply Module Status Network Activity Network Status EtherNet RJ 45 Connector PointBus Status Module Status Network Activity Status Network Status 1734 AENT PointBus Status Field Power System Pow...

Page 10: ...Status Off No power applied to device Flashing Red Green LED powerup test module self test Green Device is operating normally Flashing Red Recoverable fault has occurred Firmware NVS update Network IP...

Page 11: ...urs during powerup test Network Activity Off No link established Flashing Green Off Transmit or receive activity Steady Green Link established PointBus Status Off Device not powered check module statu...

Page 12: ...rable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me sont sujettes inspection par les autorit...

Page 13: ...an be extended beyond 1 0A by using 1734 EP24DC backplane extension Power Supplies Add multiple 1734 EP24DC modules to reach the 63 module maximum Cat No PointBus Current Requirements 1734 IB2 75mA 17...

Page 14: ...apter status PointBus status Network activity status Network status 2 green power supply status indicators System Power PointBus 5V power Field Power 24V from field supply Power Consumption 4 5W maxim...

Page 15: ...Shock IEC 60068 2 27 Test Ea Unpackaged Shock Operating 30g peak acceleration Nonoperating 50g peak acceleration Vibration IEC 60068 2 6 Test Fc Operating Tested 5g 10 500Hz ESD Immunity IEC 61000 4 2...

Page 16: ...n 2 Groups A B C and D Hazardous locations certified for US and Canada CE2 European Union 89 336 EEC EMC Directive compliant with EN 61000 6 4 Industrial Emissions EN 50082 2 Industrial Immunity EN 61...

Reviews: