Step 

 

1

Publication 177510.1 - March 1996

Configure and Ground I/O and

Processor Chassis

Configure I/O Chassis

1 2 3 4 5 6 7 8

O

N
O

F

F

First I/O group number

I/O rack number

Address Switch Assembly

(S1)

Switch Assembly (S2)

Pressed in at top 

Closed (ON)

Pressed in at bottom 

Open (OFF)

O

N
O

F

F

1 2 3 4

5 6

Switch Position

    1          2

57.6K Baud  10,000ft

115.2K Baud  5,000ft

Not Used

Maximum I/O

chassis distance

Link Response  ON for series B emulation

Scan  On for all but last 4 slots

Off for all slots

OFF for unrestricted

Always OFF

ATTENTION:

 Link response switch must

be ON when using the following scanner modules:

1775S4A

1775S4B

1775S5

1775SR5

1775SR

ON

OFF

OFF

OFF

ON

ON

ON

230.4K Baud  2,500ft

1

OFF

230.4K Baud with 1775S5 revision A/G and

later, and 1775SR5 revision A/G and later

scanners only.

Off

Set the backplane switches.

a

Keying

Bands

Install keying bands.

b

1771 I/O

Module

See the appropriate product data for the module

you are installing to determine the proper keying

positions for each module.

Summary of Contents for PLC-3 Series

Page 1: ...Quick Start for Experienced Users PLC 3 Family Programmable Controllers Allen Bradley product icon...

Page 2: ...blication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Allen Bradley office describes some important differences between...

Page 3: ...r single chassis PLC 3 2 1 Install 1775 P1 Power Supply into the PLC 3 2 3 Install Processor Memory and Scanner Modules 3 1 Connect Front Panel Cable and Install Processor 3 1 Install Memory Module s...

Page 4: ...Ground I O chassis page 1 1 a b Install 1775 P3 power supply page 2 1 Install memory module s page 4 1 Install I O scanner module s page 4 2 Install the processor module page 4 1 Install 1775 P1 power...

Page 5: ...s 1775 A1 A2 PLC 3 1775 A3 PLC 3 10 front panel cable 1775 CAK processor 1775 L4 PLC 3 10 1775 L3 PLC 3 memory module s 1775 MS4 MS8 MSA MSD PLC 3 10 1775 ME4 ME8 MEA MED MEF PLC 3 I O scanner module...

Page 6: ...er PLC 3 Programmable Controllers Installation and Operation Manual 1775 6 7 1 PLC 3 Family Programmable Controllers Programming Reference Manual 1775 6 4 1 Allen Bradley PLC 3 Power Supply 1775 P1 Pr...

Page 7: ...Response ON for series B emulation Scan On for all but last 4 slots Off for all slots OFF for unrestricted Always OFF ATTENTION Link response switch must be ON when using the following scanner module...

Page 8: ...processor module must be in chassis 0 consecutively starting with 0 O N O F F Switch 1 2 3 Chassis Number on off on on on off off off off off off off 0 1 2 3 ATTENTION Number the chassis so that chass...

Page 9: ...nnectors on the power supply module connect the 8 pin control connector cable to the power supply module and insert the power supply module in the right most slot of the chassis PLC 3 10 chassis 20418...

Page 10: ...n the power supply module and connect any relay wires then insert the PLC 3 10 module s into the chassis and turn the ac power on e Close the front door of the chassis and rotate the two retaining scr...

Page 11: ...hassis power cable to the processor chassis b Optionally connect the I O chassis to the power supply using an I O power cable c Make AC power connections Power Cable L2 120V ac L1 L2 220 240V ac L1 Ju...

Page 12: ...if you are using expansion chassis Install Memory Module s a Remove power to the processor chassis b Insert the memory module into the processor chassis guiding the module into the plastic tracks on...

Page 13: ...be in the chassis with the front panel Set the necessary switches for your application of the scanner module For information about switch settings see the user manual for your particular scanner modu...

Page 14: ...t the wires be tween the I O devices and the wiring arm terminals Trim and strip the wires as necessary and make certain that each wire is firmly in place See chapter 3 of the PLC 3 Programmable Contr...

Page 15: ...No 2 Channel No 3 Channel No 1 Blue Shield Clear Blue Shield Clear Blue Shield Clear Blue Shield Clear Terminator Cat No 1770 XT Optonal User supplied Pushbutton for I O Chassis Restart Optonal User...

Page 16: ...position b Remove the keyboard from the industrial terminal and locate the switch assembly on the front of the terminal c Connect terminal to processor using a 1775 CAT cable Front Panel CH0 or 1775 S...

Page 17: ...4 x or 5 0 monochrome or color graphics monitor installed 1785 KL KTP KT KT2 KTK1 card If your 1784 T50 has DOS version 2 11 or earlier you must upgrade to the current version of Allen Bradley DOS The...

Page 18: ...If this does not clear the situation you must troubleshoot the chassis using the PLC 3 Family Controllers Installation and Operation Manual publication number 1775 6 7 1 Specifications for PLC 3 proce...

Page 19: ...ord Data Table Size G Expandable limited only by available memory Environmental Conditions G Operational Temperature 32 to 140 F 0 to 60 C G Storage Temperature 40 to 185 F 40 to 85 C G Relative Humid...

Page 20: ...775 10 1 March 1996 Publication 1775 10 1 March 1996 Supercedes 1775 2 20 August 1988 1775 5 1 March 1995 1775 2 4 November 1985 1775 2 26 July 1988 PN 955124 60 Copyright 1996 Allen Bradley Company I...

Reviews: