Publication 1761-UM006A-EN-P - February 2001
Peer-to-Peer Messaging
5-5
Open the message instruction and enter the appropriate variables. The
variables are described in Table 5.4.
Table 5.4 Message Instruction Variables for Sending a Message to a Destination
Controller
Variable
Setting
This Controller Parameters:
Communication Command
Use any command supported by your controller.
Data Table Address
Use any valid file.
Size in Elements
For all ENI data configuration, always set this to 4 (4 words).
Channel
The RS-232 communication channel that is connected to the
ENI, typically 0 or 1.
Target Device Parameters:
Message Timeout
Leave this value at the default.
Data Table Offset
Always 0.
Local Node Addr (dec).
The destination node address, Nodes 0 to 49.
Local/Remote
Always Local.