Publication 1761-UM006A-EN-P - February 2001
ENI Configuration (Node 248 to 254)
4-7
3.
Open the message instruction and enter the appropriate
variables. The variables are described in Table 4.1.
4.
With the controller in Run, initiate the message. The new TCP/IP
information is transmitted to the ENI.
Table 4.1 Message Instruction Variables for Configuring ENI Data Parameters
Variable
Setting
This Controller Parameters:
Communication
Command
For the ENI configuration, this must be set to:
•
485CIF for MicroLogix and SLC
•
an unprotected write command for CompactLogix and
PLC-5
Data Table Address
In this example we are using integer file 50, element 5
(instruction starts at N50:5).
Size in Elements
For all ENI TCP/IP data configuration, always set this to 4 (4
words).
Channel
The RS-232 communication channel that is connected to the
ENI, typically 0 or 1.
Target Device Parameters:
Message Timeout
Leave this value at the default.
Data Table Offset
Always 0.
Local Node Addr (dec).
This is the destination node address, in this example it is 101.
Local/Remote
Always Local.
ATTENTION
!
At this point, the new configuration has NOT
been saved to permanent memory. See Node
248 information on page 4-11 for instructions.
Summary of Contents for MicroLogix 1761-NET-ENI
Page 1: ...MicroLogix Ethernet Interface ENI Cat No 1761 NET ENI User Manual...
Page 8: ...Publication 1761 UM006A EN P January 2001 Preface P 4...
Page 14: ...Publication 1761 UM006A EN P February 2001 1 6 Product Overview...
Page 50: ...Publication 1761 UM006A EN P February 2001 5 6 Peer to Peer Messaging...
Page 84: ...Publication 1761 UM006A EN P February 2001 8 6 Troubleshooting...
Page 100: ...Publication 1761 UM006A EN P February 2001 4 Index...
Page 101: ......