Publication 1764-UM001A-US-P
Communication Connections
4-9
Multiple Cable Connection
When connecting multiple cables to the DH-485 connector, use the following
diagram.
Grounding and Terminating the DH-485 Network
Only one connector at the end of the link must have Terminals 1 and 2 jumpered
together. This provides an earth ground connection for the shield of the
communication cable. Both ends of the network must have Terminals 5 and 6
jumpered together, as shown below. This connects the termination impedance (of
120
Ω
) that is built into each AIC+ as required by the DH-485 specification.
End-of-Line Termination
Table 4.3 Connections using Belden #3106A Cable
For this Wire/Pair
Connect this Wire
To this Terminal
Shield/Drain
Non-jacketed
Terminal 2 - Shield
Blue
Blue
Terminal 3 - (Common)
White/Orange
White with Orange Stripe
Terminal 4 - (Data B)
Orange with White Stripe
Terminal 5 - (Data A)
Table 4.4 Connections using Belden #9842 Cable
For this Wire/Pair
Connect this Wire
To this Terminal
Shield/Drain
Non-jacketed
Terminal 2 - Shield
Blue/White
White with Blue Stripe
Cut back - no connection
(1)
(1) To prevent confusion when installing the communication cable, cut back the white with blue stripe wire immediately
after the insulation jacket is removed. This wire is not used by DH-485.
Blue with White Stripe
Terminal 3 - (Common)
White/Orange
White with Orange Stripe
Terminal 4 - (Data B)
Orange with White Stripe
Terminal 5 - (Data A)
to Next Device
to Previous Device
Jumper
Jumper
Belden #3106A or #9842 Cable
1219 m (4000 ft) Maximum
Summary of Contents for micrologix 1500
Page 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Page 6: ...Publication 1762 RM001A US P Preface P 4...
Page 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Page 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Page 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Page 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Page 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Page 147: ...AB Spares...
Page 149: ...AB Spares...