This chapter describes how to set up communications for your control system. The
method you use and cabling required depend on your application. This chapter
also describes how the controller establishes communication with the appropriate
network. Topics include:
•
Default Communication Configuration
•
Communications Toggle Push Button
•
•
Connecting to a DH-485 Network
•
Default Communication
Configuration
The MicroLogix 1500 has the following default communication configuration.
For more information about communications, see Understanding Communication
Protocols on page E-1.
Table 4.1 DF1 Full-Duplex Configuration Parameters
Parameter
Default
Baud Rate
19.2K
Parity
none
Source ID (Node Address)
1
Control Line
no handshaking
Error Detection
CRC
Embedded Responses
auto detect
Duplicate Packet (Message) Detect
enabled
ACK Timeout
50 counts
NAK retries
3 retries
ENQ retries
3 retries
Stop Bits
1
NOTE
The default configuration is present when:
•
The controller is powered-up for the first time.
•
The communications toggle push button specifies default
communications (the DCOMM LED is on).
•
An OS upgrade is completed.
Summary of Contents for micrologix 1500
Page 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Page 6: ...Publication 1762 RM001A US P Preface P 4...
Page 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Page 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Page 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Page 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Page 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Page 147: ...AB Spares...
Page 149: ...AB Spares...