139
Publication 1766-RM001A-EN-P - October 2008
Chapter
6
Using High-Speed Outputs
The high-speed output instructions allow you to control and monitor the
PTO and PWM functions which control the physical high-speed outputs.
PTO - Pulse Train Output
Instruction Type: output
Pulse Train Output
Function
The MicroLogix 1400 1766-L32BXB and 1766-L32BXBA controller supports
three high-speed outputs. These outputs can be used as standard outputs
(not high-speed) or individually configured for PTO or PWM operation.
The PTO functionality allows a simple motion profile or pulse profile to
be generated directly from the controller. The pulse profile has three
primary components:
•
Total number of pulses to be generated
Instruction
Used To:
Page
PTO - Pulse Train Output
Generate stepper pulses
PWM - Pulse Width Modulation
Generate PWM output
PTO
Pulse Train Output
PTO Number
0
PTO
IMPORTANT
The PTO function can only be used with the controller’s embedded I/O. It
cannot be used with expansion I/O modules.
IMPORTANT
The PTO instruction should only be used with MicroLogix 1400 BXB or BXBA
units. Relay outputs are not capable of performing very high-speed
operations.
Execution Time for the PTO Instruction
Controller
When Rung Is:
True
False
MicroLogix 1400
11.0210 µs
5.5115 µs
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive