background image

2

    FLEX™ I/O Isolated Input/Output Analog Module

Publication 1794-IN039F-EN-P - November 2011

European Hazardous Location Approval 

North American Hazardous Location Approval

The 1794-IF2XOF2I module is hazardous location approved. 

Install the Analog Input/Output Module 

The module mounts on a 1794 terminal base.

1.

Rotate the keyswitch (3) on the terminal base (4) clockwise to position 5 as 
required for this type of module.

2.

Make sure the FlexBus connector (1) is pushed all the way to the left to 
connect with the neighboring terminal base/adapter. 

You cannot install 

the module unless the connector is fully extended.

3.

Make sure the pins on the bottom of the module are straight so they will 
align properly with the connector in the terminal base.

4.

Position the module (7) with its alignment bar (6) aligned with the groove 
(5) on the terminal base.

5.

Press firmly and evenly to seat the module in the terminal base unit. The 
module is seated when the latching mechanism (2) is locked into the 
module. 

Connect Wiring for the Analog Inputs and Outputs

1. 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, and 1794-TB3TS: 

Connect individual input/output wiring to numbered terminals on the 
0…15 row (A) as indicated in the 

Wiring Connections for 1794-IF2XOF2I 

Input/Output Module

 table. Use Belden 8761 cable for signal wiring.

1794-TBN:

 Connect individual input/output wiring to even-numbered 

terminals on the 16…33 row (B) as indicated in the 

Wiring Connections 

for 1794-IF2XOF2I Input/Output Module

 table. Use Belden 8761 cable 

for signal wiring.

ATTENTION

 

If multiple power sources are used, do not exceed the specified isolation 
voltage.

The following applies when the product bears the Ex Marking.

This equipment is intended for use in potentially explosive atmospheres as defined by 
European Union Directive 94/9/EC and has been found to comply with the Essential Health 
and Safety Requirements relating to the design and construction of Category 3 equipment 
intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this 
Directive.
Compliance with the Essential Health and Safety Requirements has been assured by 
compliance with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional certification requirements:

This equipment is not resistant to sunlight or other sources of UV 

radiation.

This equipment must be installed in an enclosure providing at least 

IP54 protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined by 

Rockwell Automation.

This equipment must be used only with ATEX certified Rockwell 

Automation terminal bases.

Secure any external connections that mate to this equipment by using 

screws, sliding latches, threaded connectors, or other means provided 
with this product.

Do not disconnect equipment unless power has been removed or the 

area is known to be nonhazardous.

Provision shall be made to prevent the rated voltage from being 

exceeded by transient disturbances of more than 40% when applied in 
Zone 2 environments.

The following information applies 
when operating this equipment in 
hazardous locations:

Informations sur l’utilisation de cet 
équipement en environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D” 
are suitable for use in Class I Division 2 
Groups A, B, C, D, Hazardous Locations and 
nonhazardous locations only. Each product is 
supplied with markings on the rating 
nameplate indicating the hazardous location 
temperature code. When combining 
products within a system, the most adverse 
temperature code (lowest “T” number) may 
be used to help determine the overall 
temperature code of the system. 
Combinations of equipment in your system 
are subject to investigation by the local 
Authority Having Jurisdiction at the time of 
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" 
ne conviennent qu’à une utilisation en 
environnements de Classe I Division 2 Groupes 
A, B, C, D dangereux et non dangereux. Chaque 
produit est livré avec des marquages sur sa 
plaque d’identification qui indiquent le code de 
température pour les environnements 
dangereux. Lorsque plusieurs produits sont 
combinés dans un système, le code de 
température le plus défavorable (code de 
température le plus faible) peut être utilisé pour 
déterminer le code de température global du 
système. Les combinaisons d’équipements dans 
le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de 
l’installation.

WARNING

EXPLOSION HAZARD

Do not disconnect equipment unless 

power has been removed or the area 
is known to be nonhazardous. 

Do not disconnect connections to 

this equipment unless power has been 
removed or the area is known to be 
nonhazardous. Secure any external 
connections that mate to this 
equipment by using screws, sliding 
latches, threaded connectors, or other 
means provided with this product.

Substitution of components may 

impair suitability for Class I,

Division 2.

If this product contains batteries, 

they must only be changed in an area 
known to be nonhazardous.

AVERTISSEMENT

RISQUE D’EXPLOSION

Couper le courant ou s’assurer que 

l’environnement est classé non dangereux 
avant de débrancher l'équipement.

Couper le courant ou s'assurer que 

l’environnement est classé non dangereux 
avant de débrancher les connecteurs. 
Fixer tous les connecteurs externes reliés 
à cet équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou autres 
moyens fournis avec ce produit.

La substitution de composants peut 

rendre cet équipement inadapté à une 
utilisation en environnement de Classe I, 
Division 2.

S’assurer que l’environnement est 

classé non dangereux avant de changer 
les piles.

Description

Description

1

FlexBus connectors

5

Groove

2

Latching mechanism

6

Alignment bar

3

Keyswitch

7

Module

4

Terminal base

ATTENTION

Do not remove or replace a Terminal Base unit while power is applied. 
Interruption of the backplane can result in unintentional operation or 
machine motion.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use zinc 
plated yellow-chromate steel DIN rail to assure proper grounding. The use 
of other DIN rail materials (for example, aluminum or plastic) that can 
corrode, oxidize, or are poor conductors, can result in improper or 
intermittent grounding. Secure DIN rail to mounting surface approximately 
every 200 mm (7.8 in.) and use end-anchors appropriately.

ATTENTION

Connect only one current or one voltage signal per channel. Do not 
connect both current and voltage on one channel.

45284

6

5

4

3

2

1

7

Summary of Contents for FLEX 1794-IF2XOF2I

Page 1: ...age Category II applications as defined in IEC publication 60664 1 at altitudes up to 2000 m 6562 ft without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance ...

Page 2: ...e cet équipement en environnements dangereux Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code lowest T number may...

Page 3: ... 33 are internally connected in the terminal base unit 1794 TB3T 1794 TB3TS Terminals 16 17 19 21 23 25 27 29 31 and 33 are internally connected in the terminal base unit V DC power 1794 TB3 1794 TB3S Terminals 34 51 are internally connected in the terminal base unit 1794 TB3T 1794 TB3TS Terminals 34 35 50 and 51 are internally connected in the terminal base unit 1794 TBN 1794 TB2 Terminals 34 and...

Page 4: ...it 1 0 0 0 1 4 20 mA 7 5 ms 5 0 ms 0 0 1 0 10V 2 5 ms 2 5 ms 0 0 1 1 5V 2 5 ms 2 5 ms 0 1 0 0 0 20 mA 7 5 ms 5 0 ms 0 1 0 1 4 20 mA 7 5 ms 5 0 ms 0 1 1 0 0 10V 5 0 ms 5 0 ms 0 1 1 1 10V 5 0 ms 5 0 ms 1 0 0 0 0 20 mA 2 5 ms 2 5 ms 1 0 0 1 4 20 mA 7 5 ms 5 0 ms 1 0 1 0 0 10V 2 5 ms 2 5 ms 1 0 1 1 0 5V 2 5 ms 2 5 ms 1 1 0 0 20 mA 2 5 ms 2 5 ms 1 1 0 1 4 20 mA 7 5 ms 5 0 ms 1 1 1 0 10V 2 5 ms 2 5 ms 1...

Page 5: ... non linearity and repeatability error terms 2 If 24V DC is removed from the module input resistance 10 k Output Specifications Attribute Value Number of outputs 2 isolated Resolution Voltage Current 15 bits plus sign 0 320 mV cnt 0 656 A cnt General Specifications Data format 2 s complement 2 s complement Binary Offset binary Conversion type Digital to analog converter Update rate 2 5 5 0 ms all ...

Page 6: ... Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 X CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 ...