28
ControlNet-to-DeviceNet Linking Device
1788-5.2B - October 1999
Module STATUS LED
The Module Status LED indicates whether the CN2DN is powered, configured,
and operating properly. Table A shows how to interpret the Module Status LED
states.
Standby state (flashing green) indicates the CN2DN module has passed all self
tests and is ready to operate, but is not configured.
Operational state (steady green) indicates the CN2DN module has left standby
state because the necessary network configuration has occurred.
Linking Activity LED
The Linking Activity LED indicates the rate of traffic through the bridge. Table B
shows how to interpret the Linking Activity Status LED states.
Table A Interpretation of the Module Status LED
LED State
Meaning
Off
No power to device
Flashing green
Standby state
Steady green
Operational state
Flashing red
Major recoverable fault
Steady red
Major unrecoverable fault
Table B Interpretation of the Linking Activity LED
LED State
Meaning
Off
No traffic
Flashing green
Traffic present (flash rate reflects amount of traffic)
Flashing red and green
Module is running boot code only (reduced
functionality code only for FLASH upgrading)