Allen-Bradley ControlLogix Installation Instructions Manual Download Page 3

Rockwell Automation Publication 1756-IN620D-EN-P - October 2018

3

ControlLogix Redundant Power Supply

Before You Begin

ATTENTION: 

Before installing, configuring, operating, or maintaining this product, read this document and the documents listed in the additional resources 

section for installing, configuring, or operating equipment. Users should familiarize themselves with installation and wiring instructions in addition to 
requirements of all applicable codes, laws, and standards. 

Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with 
applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for 
repair. Do not dismantle the module.

This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F) [PA75R, PB75R, PSCA2] -25…+70 °C 
(-13…+158 °F) [PAXTR, PBXTR, PSCA2XT]. The equipment must not be used outside of this range.

Annunciator cable length should be less than 10 m (32.8 ft).

Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

Environment and Enclosure

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in 

IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such 
environments.

This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific 
environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must 
have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the 
application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain 
additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

In addition to this publication, see the following:

• Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

, for additional installation requirements.

• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous 
locations.

Informations sur l’utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, 
D, Hazardous Locations and nonhazardous locations only. Each product is supplied with 
markings on the rating nameplate indicating the hazardous location temperature code. When 
combining products within a system, the most adverse temperature code (lowest "T" number) 
may be used to help determine the overall temperature code of the system. Combinations of 
equipment in your system are subject to investigation by the local Authority Having Jurisdiction 
at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en 
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque 
produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de 
température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un 
système, le code de température le plus défavorable (code de température le plus faible) peut être 
utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements 
dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de 
l'installation.

WARNING: Explosion Hazard

• Do not disconnect equipment unless power has been removed or the 

area is known to be nonhazardous. 

• Do not disconnect connections to this equipment unless power has 

been removed or the area is known to be nonhazardous. Secure any 
external connections that mate to this equipment by using screws, 
sliding latches, threaded connectors, or other means provided with this 
product.

• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area 

known to be nonhazardous.

AVERTISSEMENT: Risque d’Explosion

• Couper le courant ou s'assurer que l'environnement est classé non 

dangereux avant de débrancher l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non 

dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs 
externes reliés à cet équipement à l'aide de vis, loquets coulissants, 
connecteurs filetés ou autres moyens fournis avec ce produit.

• La substitution de composants peut rendre cet équipement inadapté à une 

utilisation en environnement de Classe I, Division 2.

• S'assurer que l'environnement est classé non dangereux avant de changer 

les piles.

Summary of Contents for ControlLogix

Page 1: ...rom one or two ControlLogix redundant power supplies to the single power connector on the ControlLogix chassis backplane RedundantPowerSupplyandChassisCompatibility Your chassis series determines the redundant power supply that you can use This table lists the chassis that can be installed with each redundant power supply Topic Page Summary of Changes 5 Components of the Redundant System 5 Tools R...

Page 2: ...code de pratique en vigueur Si cet équipement est utilisé d une façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise 㭒㦮 a G㩲䛞G 䂮 SG 㩫 SG㧧 G G㥶㰖G 㑮䞮 G㩚㠦G Gⶎ G䙂䞾䞮㡂G 䂮 SG 㩫G G㧧 㠦Gὖ䞲G㺎ἶG㧦 G 㦮Gⶎ 㦚G 㔲G㧓ἶG㑯㰖䞮 㕃㔲㡺 UG 㣿㧦 G Gὖ G 㩫 SG G G䚲㭖㠦 G㣪ῂ䞮 G 䟃㠦G 䟊G 㔲G 䂮G G G㰖䂾㦚G㑯㰖䟊㟒G䞿 U 䂮 SG㫆㩫 SGṖ SG 㣿 SG㫆Ⱃ SG 䟊 SG㥶㰖 㑮G G G㧧㠛㦖Gὖ G 㩫㠦G G㩗㩞䞲Gᾦ㥷㦚G 㦖G 㣿㧦 G䐋䟊 ⰢG㑮䟟䟊㟒G䞿 U...

Page 3: ... 250 and EN IEC 60529 as applicable for explanations of the degrees of protection provided by enclosures North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations Informations sur l utilisation de cet équipement en environnements dangereux Productsmarked CLI DIV2 GPA B C D aresuitableforuseinClassIDivision2GroupsA B C D Hazard...

Page 4: ...ed or the area is known to be nonhazardous Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140 of the rated voltage when applied in Zone 2 environments This equipment must be used only with ATEX IECEx certified Rockwell Automation backplanes The instructions in the user manual shall be observed IEC Hazardous Location Approval The foll...

Page 5: ...xredundantpowersupplysystemisdesignedtoaccountforoperationalanomaliesinonlythepowersupply Thechassisadapterandpower supply cables are excluded Item Description Cat No 1 Redundant power supply 1756 PA75R A and or 1756 PB75R A or 1756 PAXTR and or 1756 PBXTR 2 Redundant power supply cable Length 0 91 m 3 ft 1756 CPR2 2 3 or 1756 CPR2D 3 4 or 1756 CPR2U 3 4 2 Cable bend radius is 12 7 cm 5 0 in 3 Cab...

Page 6: ...onal power supplies 3 18 mm 0 125 in slotted screwdriver Crimper 6 35 mm 0 25 in slotted or 2 Phillips screwdriver Wire stripper Torque screwdriver Drill Needle nose pliers IMPORTANT Installthechassisintheenclosureandmakesurethatyoufollowtheminimumspacingrequirements SeetheControlLogixChassisInstallationInstructions publication 1756 IN621 for more information WARNING EXPLOSION HAZARD If you connec...

Page 7: ...to connect power Tighten the terminals to a torque of 0 565 N m 5 lb in WARNING EXPLOSION HAZARD Ifyouconnectordisconnectthe1756 CPR2cableswhileeitherbackplanepowersourceison anelectricarccanoccur Thiscouldcauseanexplosioninhazardous location installations Repeated electric arcing causes excessive wear to contacts on both the module and its mating connector Worn contacts may create electrical resi...

Page 8: ...ator function connect a compatible source voltage to a contact terminal Then connect the other terminal to the monitoring or signaling device IMPORTANT The voltage input connections of the power supplies are auto sensing You do not use a jumper for example a 120 240V AC jumper when connecting external power to the power supply as shown in the previous figure Item Description 1756 PA75R A AC Descri...

Page 9: ...solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max 5 Plastic barrier ATTENTION Make sure the power supply is mounted and all panel fabrication is complete before you remove the protective label This label protects the power supply from metal shavings falling inside the power supply and damaging it during operation Routing of annunciator cable when annunciato...

Page 10: ...r supply is operating properly but is the only power supply providing power to the chassis adapter Check the other power supply Off Solid amber All possible connections are made but the power supply is turned off Turn the power supply ON If the power supply does not turn ON follow these steps 1 Remove the input power from the power supply 2 Wait 30 seconds 3 Reconnect the input power 4 Turn the po...

Page 11: ...N the replacement redundant power supply the connected chassis automatically draws power from the redundant power supplies RemoveorReplaceaChassisAdapter Use this information to remove or replace a chassis adapter RemoveaChassisAdapter Follow these steps to remove a chassis adapter 1 Turn the redundant power supplies OFF 2 Disconnect the power cable at the chassis adapter 3 Push the top and bottom...

Page 12: ...sistive only 240V AC 50 60 HZ 240V DC 50 mA resistive only 90V DC for ATEX IECEx Isolation voltage N A 250V continuous Reinforced InsulationType Power Input to Backplane Power Input to Annunciator Annunciator to Backplane All supply frequencies or frequency ranges if AC supply is used N A 47 63 Hz N A 47 63 Hz N A Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Ope...

Page 13: ...ical Data publication 1756 TD003 Describes Ethernet communication module specifications ControlLogix Chassis Installation Instructions publication 1756 IN621 Provides information on installing ControlLogix chassis ControlLogix System User Manual publication 1756 UM001 Provides instructions for installation and use of ControlLogix Systems application design and other general information for these s...

Page 14: ...14 Rockwell Automation Publication 1756 IN620D EN P October 2018 ControlLogix Redundant Power Supply Notes ...

Page 15: ...Rockwell Automation Publication 1756 IN620D EN P October 2018 15 ControlLogix Redundant Power Supply Notes ...

Page 16: ...n needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How toVideos FAQs Chat User Forums and Product Notification Updates https rockwellautomation custhelp com LocalTechnical Support Phone Numbers Loc...

Reviews: