Rockwell Automation Publication 1756-IN065A-EN-P - September 2017
9
ControlLogix DeviceNet Scanner Module
Specifications
Attribute
1756-DNB, 1756-DNBK
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)
Temperature, surrounding air, max.
60 °C (140 °F)
Voltage and current ratings
Backplane: 5.1V DC, 400 mA
DeviceNet Power: 60 mA @ 11...2V DC CL 2/SELV limited to 100VA
Isolation voltage
50V (continuous),Basic Insulation Type, DeviceNet to Backplane
No isolation between USB and Backplane
Type tested at 860V AC for 60 s
Terminal block torque specs
DeviceNet connector: 0.56…0.79 N•m (5…7 lb•in)
Enclosure type rating
None (open-style)
North American temp code
T4A
ATEX Temp Code
T4