Publication 1769-UM005A-EN-P
5-6
Diagnostics and Troubleshooting
Error Codes
The table below explains the extended error code.
Table 5.3 Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-
Specific Error
X300
001
1 0000 0000
General hardware error, loss of external 24V dc power
X301
001
1 0000 0001
Hardware ROM error
X302
001
1 0000 0010
Hardware EEPROM error
X303
001
1 0000 0011
Channel 0 calibration error
X304
001
1 0000 0100
Channel 1 calibration error
X305
001
1 0000 0101
Channel 2 calibration error
X306
001
1 0000 0110
Channel 3 calibration error
X307
001
1 0000 0111
Channel 4 calibration error
X308
001
1 0000 1000
Channel 5 calibration error
X309
001
1 0000 1001
Channel 0 Analog/Digital Converter error
X30A
001
1 0000 1010
Channel 1 Analog/Digital Converter error
X30B
001
1 0000 1011
Channel 2 Analog/Digital Converter error
X30C
001
1 0000 1100
Channel 3 Analog/Digital Converter error
X30D
001
1 0000 1101
Channel 4 Analog/Digital Converter error
X30E
001
1 0000 1110
Channel 5 Analog/Digital Converter error
Summary of Contents for Compact 1769-IR6