14
POINT I/O Protected Output Module
Publication 1734-IN586B-EN-P - March 2002
Specifications - 1734-OB2EP/C Protected Output Module
Output Specifications -
Meets IEC 1+ 24V dc Output Specifications
Number of Outputs
2 (1 group of 2) non-isolated, sourcing
ON-State Voltage Range
10V dc minimum
24V dc nominal
28.8V dc maximum
ON-State Voltage Drop
0.7V dc maximum (at 28.8V dc, 55°, full load
condition)
ON-State Current
1.0mA minimum per channel
OFF-State Voltage
28.8V dc maximum
OFF-State Leakage
0.5mA maximum
Output Signal Delay
1
OFF to ON
ON to OFF
0.1ms maximum
0.1ms maximum
Output Current Rating
Maximum 2.0A per output
4.0A maximum per module
Surge Current
2A maximum, electronically protected
Indicators (field side indication,
logic driven)
2 yellow output status;
2 red output fault
2 green/red module/network status
Keyswitch Position
1
General Specifications
Module Location
1734-TB or -TBS wiring base assembly
Pointbus Current
75mA maximum @ 5V dc
Power Dissipation
3.4W maximum @ 28.8V dc
Thermal Dissipation
11.6 BTU/hr maximum @ 28.8V dc
Isolation Voltage
50V continuous (Tested to 1250V ac for 60s
between outputs and Pointbus)
External dc Power
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10 to 28.8V dc
8mA
Dimensions Inches
(Millimeters)
2.21H x 0.47W x 2.97L
(56.0H x 12.0W x 75.5L)